Calibration troubleshooting, Installation guide current monitoring h906 – Veris Industries H906 Install User Manual
Page 4
Z201573-0D
Page 4 of 4
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07132
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Current Monitoring
H906
TM
Before beginning calibration, establish normal load conditions. Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
1. Turn setpoint screw clockwise
until Status Open LED turns
on.
Status
Closed
Status
Open
Setpoint
2. Slowly turn the screw counter
clockwise until the Status
Closed LED turns on.
Status
Closed
Status
Open
Setpoint
3. Turn the screw an additional
¼ turn counter clockwise for
operational margin.
¼
Status
Closed
Status
Open
Setpoint
B. To monitor over-current (mechanical problems, seized impeller)
1. Turn setpoint screw counter
clockwise until Status Closed
LED turns on.
Status
Closed
Status
Open
Setpoint
2. Slowly turn the setpoint screw
clockwise until the Status
Open LED just turns on.
Status
Closed
Status
Open
Setpoint
3. Turn the setpoint screw an
additional ¼ turn clockwise
for operational margin.
¼
Status
Closed
Status
Open
Setpoint
Calibration
Troubleshooting
Problem
Solution
No Reading at Controller
• Check sensor calibration (see above)
• Check for control voltage at sensor (5VDC
• Verify correct polarity
• Assure that sensor core mating surfaces are clean and that the core clamp is completely closed
Setpoint screw has no stops
The setpoint screw has a slip-clutch at both ends of its travel to avoid damage. Twenty turns CCW will
reset the sensor to be most sensitive. Repeat calibration above.
Both LEDs are lit
Setpoint screw is too far clockwise. See solution above.