Veris Industries MSC SERIES Datasheet User Manual
Ceiling mount occupancy sensors, Msc series, Lighting c ontr ols
![background image](/manuals/259860/1/background.png)
LIGHTING C
ONTR
OLS
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Ceiling Mount
Occupancy Sensors
DESCRIPTION
MSC Series Occupancy Sensors employ passive infrared (PIR) and/or ultrasonic
technologies to accurately detect occupancy and automatically switch room lighting.
The low-profile sensor is ceiling-mounted to maximize motion sensitivity in large
areas with obstructions. With a 360 degree field of view, and up to 2000 square
feet of coverage area, the ceiling-mounted occupancy sensor is ideal for conference
rooms, classrooms, multi-stall bathrooms, and large office areas.
The MSC series also incorporates an integral photosensor to prevent lights from
switching on when sufficient ambient light is present, as commonly found in
windowed areas.
Installation and configuration are simple. The sensor readily mounts to drop ceilings,
and it features front adjustments for setting sensitivity and time delay. The sensor
also features an auxiliary relay for use with building automation and HVAC systems.
APPLICATIONS
●
Lighting control based on occupancy
●
Reducing energy usage
●
Key component for LEED* certification programs
●
MSC1000 – best for conference rooms, classrooms, and other
general applications
●
MSCD2000 – best for multi-stall bathrooms, large conference rooms,
and warehouses
●
MSCU2000 – best for lobbies, aisles, and great for multi-stall bathrooms
FEATURES
●
Up to 2000 square foot coverage area
●
360 degree field of view
●
Daylight level sensing (from 0.5 to 250 foot-candles)...eliminates
unneccessary lighting
●
Adjustable time delay (preset time delays from 15 seconds [test] to 30
minutes)...provides ultimate flexibility
●
Adjustable coverage sensitivity (from 60-100%)
●
Auxiliary relay...easily communicates with building control system
●
Adjustment compartment cover
●
LED motion indicator...provides quick visual status
●
Manual bypass...for easy commissioning
Uses The Latest Passive Infrared
And Ultrasonic Technologies
SPECIFICATIONS
Standards
UL and cUL Listed; FCC part 15 (Class B) for Home and Office Use
Input Voltage
24VDC
Current Consumption@24VDC*:
PIR
21mA nominal
Ultrasonic
34mA nominal
Dual
37mA nominal
Isolated Relay
Contact rating: 1A@24VDC Resistive
Temperature
0° to 50°C (32° to 122°F)
Humidity
Max. 90% RH noncondensing
Dimensions:
MSCU
4.6” (117 mm) diameter, 1.4” (35.1 mm) high
MSCD/MSCP
4.6” (117 mm) diameter, 1.8” (45.7 mm) high
For local line switching control, power must be provided by AA47 Power Pack or an approved equivalent.
*Leadership in Energy and Environmental Design (LEED) is a registered mark of the US Green Building Council
Year
Warranty
1
Coverage Patterns for 9 ft (2.8m) Ceiling Height
PIR Sensor
Ultrasonic Sensor
MSCU
MSCD
Minor Motion
Major Motion
25 ft
(7.7m)
32 ft
(9.8m)
48 ft
(14.7m)
30 ft
(9.2m)
24 ft
(7.4m)
42 ft
(12.8m)
MSC SERIES
HQ0001801.B 01131