INSTALLATION GUIDE

H723HC

Z205458-0A

PAGE 2

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

09083

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

< 5A (H723HC min.)

0.5A

10x

50A

Controller: 0.625A/mA + 4mA
Amps ÷ Turns
(5A ÷ 10) = 0.5A
H723HC: 5A max. (10T)

2A

0.5A

300A:

5A

300A

5A

50A

Controller:
CT max ÷ H723HC max
300 ÷ 50 = 6x
10VDC -> 300A

300 A

opEration

The H723HC is a current transducer that senses current (amperage) in any of three
field-selectable ranges: 0-50, 0-100, or 0-200 amperes. These ranges represent
the maximum current that can be applied to the monitored conductor. The H723HC
transforms the monitored current into a 0-10 VDC output suitable for connection to
building controllers or other appropriate data acquisition equipment. The H723HC
requires no 12-30VDC external power to generate its output.

notEs

troublEshooting

For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

• Controller must be
programmed to account for the
extra turns. e.g., if four turns
pass through the sensor (as
shown) the normal controller
reading must be divided by 4.

DANGER: 5A CTs can present hazardous voltages.

Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.

H681x-5A CT

> 200A (H723HC max.)

For load currents greater than sensor maximum rating:
Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of

turns through the sensing window using the following

formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps

e.g. : 30A ÷ 4 Turns = 7.5 Amps max. in monitored conductor

Failure to follow these instructions can result in overheating

and permanent equipment damage.

0A

50, 100, or 200 A

SENSED AMPS

SENSOR

OUTPUT

10V

0V

10 wraps

Amperage Range
Selector Switch

200
100
50

200
100
50

Problem

Solution

No Reading at Controller

• Check polarity of sensor output connections
• Check for output voltage at sensor
• Check for amperage in monitored conductor
• Assure that sensor core mating surfaces are clean and

that the core clamp is completely closed

calibration/scaling

Set the amperage range selector switch to a level appropriate for your load. The
H723LC is available with three choices, 0-10, 0-20, or 0-40 Amps.

DDC

CONTROLLER

AI

COMM

0-10VDC Input

CAUTION: Consult
instructions prior
to installation

!

Use min. 75º C insulated conductor

ig20

AMPERAGE

RANGE

40
20
10

OUTPUT
0-10VDC

+ –

+

Self-Powered Output

Scale the output as shown below.

Wiring