Veris Industries H10F Datasheet User Manual
Current switch: auto calibration, process control, Automatically learns at initial power-up, H10f
current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye TruStat H10F is a microprocessor based, self-learning, self-calibrating
current switch. It provides calibration-free status, for both under-current and over-
current conditions. At initial power-up, the H10F automatically learns the average
current on the line with no action required by the installer. Once a current is learned,
the switch monitors for changes in current greater than ±20% of the learned load.
APPLICATIONS
●
Verifying lighting circuit and other electrical service run times
●
Monitoring status of industrial process equipment
●
Monitoring status of critical motors (compressor, fuel, etc.)
FEATURES
●
Automatic adjustable trip point (3.5-100A)...precise control of current trip point
●
100% solid state...no moving parts to fail
●
Removable mounting bracket for installation flexibility
●
5-year warranty
●
Automatic calibration...reduced errors and installation costs
●
Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
●
Monitors current for both under- and over-load in one package
●
Small size fits easily inside small starter enclosures...saves space
Automatically Learns At
Initial Power-Up
Current Switch: Auto
Calibration, Process Control
ALARM RESET
5% Typical
+20%
+15%
POWER
ON
POWER LOSS
ØAAC
ØAAC
-15%
-20%
LEARN
(MODE)
30 SEC
ALARM
(MODE)
ALARM
(MODE)
NORMAL
(CURRENT
MONITOR
MODE)
NORMAL
(CURRENT
MONITOR MODE)
NOMINAL
LEARNED
CURRENT
1 SEC. DELAY 30 SEC. DELAY
Maximize Reliability
Minimize Installed Cost
Year
Warranty
5
H10F
Hawkeye
®
TruStat™
SPECIFICATIONS
Sensor Power
Induced from monitored conductor
Isolation
600VAC RMS (UL); 300VAC RMS (CE)
Temperature Range
-15° to 60° C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Frequency Range
50/60 Hz
Trip Point Calibration Learn Period
30 sec. learn period
Normal-to-Alarm Status Output Delay
1 second max.
Alarm-to-Normal Status Output Delay
30 seconds nominal*
Status Output
±20% of learned current to trigger alarm; ±15% of learned current to release alarm (see graph)
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
*If current switch experiences a momentary loss of power, 30 second delay may or may not apply.
Do not use the LED status indicators as evidence of applied voltage.
PRODUCT FUNCTIONS
H10F
HQ0001757.B 01131