Product identification (cont.), Specifications, Installation guide temperature t series – Veris Industries T SERIES Install User Manual
Page 2

Z203672-0C
Page 2 of 7
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Temperature
T Series
TM
TA
Flexible
Probe Length
M = 6' (1.8 m)
H = 12' (3.6 m)
J = 24' (7.3 m)
Sensor Type
= 10mV/°C, Linitemp
Cal Certificate
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
P
TD
Probe Length
B = 4" (102mm)
C = 6" (152mm)
D = 8" (203mm)
E = 12” (305mm)
F = 18” (457mm)
G = 24” 610mm)
K = 36” (914mm)
Cal Certificate
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
Sensor Type
Output
= Resistive out
= 10mV/°C, Linitemp
RØ
P
Product Identification
(cont.)
Thermowell
Sensor Type
T I
Immersion Probe
Length “L”
0 = None
1 = Add Thermowell
= 10mV/°C, Linitemp
A = 2 1/2" (64mm)
B = 4" (102mm)
C = 6" (152mm)
D = 8" (203mm)
E = 12” (305mm)
Enclosure
D = Duct
G = Service Entry Body
H = Threaded NPT Only
W = Water resistant
housing
Thermowell Sizing
Probe Length
Thermowell Length
A (2 1/2") (64mm)
1 1/2” (38mm)
B (4") (102mm)
3” (76mm)
C (6") (152mm)
5” (127mm)
D (8") (203mm)
7” (178mm)
E (12”) (305mm)
11” (279mm)
P
Cal Certificate
Threads
Blank = NPT
A = BSPT
B = DIN 2999
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
Options
Input Power 5 to 30 VDC
Output 10 mV/°C
Operating Temperature -25° to 105°C (-13° to 221°F)
ACCURACY
Calibration Error 1.5°C typical; 2.5°C max. at 25°C*
Error Over Temperature 1.8°C typical; 3.0°C max. over 0° to 70°C range
2.0°C typical; 3.5°C max. over -25° to 105°C range
* Room temperature error documented on each unit.
Specifications
Bracket
Diameter
TB
A = 2 ½" (6.4 cm) max.
D = 8" (20 cm) max.
E = 12” (31 cm) max.
Cal Certificate
0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation
Sensor Type
= 10mV/°C, Linitemp
P