Temperature

T Series

TM

TA

Flexible

Probe Length

M = 6' (1.8 m)
H = 12' (3.6 m)
J = 24' (7.3 m)

Sensor Type

= 10mV/°C, Linitemp

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

P

TD

Probe Length

B = 4" (102mm)
C = 6" (152mm)
D = 8" (203mm)
E = 12” (305mm)
F = 18” (457mm)
G = 24” 610mm)
K = 36” (914mm)

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Sensor Type

Output

= Resistive out

= 10mV/°C, Linitemp

P

Product Identification
(cont.)

Thermowell

Sensor Type

T I

Immersion Probe
Length “L”

0 = None
1 = Add Thermowell

= 10mV/°C, Linitemp

A = 2 1/2" (64mm)
B = 4" (102mm)
C = 6" (152mm)
D = 8" (203mm)
E = 12” (305mm)

Enclosure

D = Duct
G = Service Entry Body
H = Threaded NPT Only
W = Water resistant
housing

Thermowell Sizing

Probe Length

Thermowell Length

A (2 1/2") (64mm)

1 1/2” (38mm)

B (4") (102mm)

3” (76mm)

C (6") (152mm)

5” (127mm)

D (8") (203mm)

7” (178mm)

E (12”) (305mm)

11” (279mm)

P

Cal Certificate

Threads

Blank = NPT
A = BSPT
B = DIN 2999

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Options

Input Power 5 to 30 VDC

Output 10 mV/°C

Operating Temperature -25° to 105°C (-13° to 221°F)

ACCURACY

Calibration Error 1.5°C typical; 2.5°C max. at 25°C*

Error Over Temperature 1.8°C typical; 3.0°C max. over 0° to 70°C range

2.0°C typical; 3.5°C max. over -25° to 105°C range

* Room temperature error documented on each unit.

Specifications

Bracket

Diameter

TB

A = 2 ½" (6.4 cm) max.
D = 8" (20 cm) max.
E = 12” (31 cm) max.

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Sensor Type

= 10mV/°C, Linitemp

P