Veris Industries Hx06 SERIES Datasheet User Manual
Hx06 series, Current monit oring

current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Current Switches: Adjustable
Trip Point, N.C. Output
Year
Warranty
5
DESCRIPTION
Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable,
and maintenance-free fan and pump status indication.
APPLICATIONS
●
Monitoring fans, pumps, motors, and other electrical loads for proper operation
●
Detecting belt loss and motor failure...ideal for fan and pump status
●
Verifying lighting circuit loads
●
Monitoring critical motors (compressor, fuel, etc.)
●
Monitoring industrial process equipment status (OEM)
FEATURES
●
Adjustable trip point...4 amperage range options for versatility
●
Easier to install than differential pressure switches...no tubing needed
●
100% solid-state, no moving parts to fail
●
Output status LEDs for fast setup
●
Adjustable mounting bracket on the solid-core housing...easy placement
●
Self-gripping iris on the split-core housing for easy installation
●
Bracket on H906 can be installed in three different configurations...added
flexibility
●
5-year warranty
Detect Belt Loss, Coupling
Shear, And Mechanical Failure
SPECIFICATIONS
Sensor Power 5-30VDC
Insulation Class
600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range
50/60 Hz
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Hysteresis
10% Typical
Off State Leakage
34μA@5VDC, 200µA@30VDC
On State Voltage Drop
1.9VDC [email protected]
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage
Maximize Reliability
Minimize Installed Cost
H906
H606
H806
H706
Hx06 SERIES
TM
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
Calibrated
Trip Point
Off
Off
Fan/pump
On
Loss of Belt/Coupling Shear
Electrical
Failure
HQ0001756.B 01131