Current monit oring, How it works, Dimensional drawing – Veris Industries H614 Datasheet User Manual
Page 2: Application/wiring diagram, Ordering information, Accessories

current monit
oring
800.354.8556
+1 503.598.4564
www.veris.com
HOW IT WORKS
The H614 is designed for HVAC fan and blower systems, as well as some pumping
systems involving consistent viscosity liquids. If an H614 is installed on one phase
of the VFD, it detects changes in that phase that result from the VFD compensating
for changes elsewhere in the system. Alternatively, for increased sensitivity, H614s
can be used on all three phases for immediate detection of phase balance changes
anywhere in the system.
During setup, the H614 automatically determines the normal amperage and
frequency profile and stores it in nonvolatile memory. Then the microprocessor
monitors for amperage changes greater than ±20% of this learned curve.
Sensor Mode
Status LED Blink Pattern
Learning Mode (first 15 sec of operation after
frequency stabilizes)
Alternating Red/Green (1 per sec.)
On/Off Status only; Learn mode incomplete.
VFD system does not meet abnormal condition
detection criteria
Green blink (5 times per sec. after
15 sec of stable frequency)
Status OK
Green blink (1 per sec.)
Alarm
Red blink (1 per sec.)
MODEL AMPERAGE
RANGE
FREQUENCY
RANGE
STATUS OUTPUT NOMINAL TRIP POINT
TARGET RANGE
HOUSING STATUS
LED
UL
CE
RoHS
H614
1.5 - 150A
12 - 115 Hz
N.O. 1.0A@30VAC/DC
±20%
Split-core
n
n
1
n
n
DIMENSIONAL DRAWING
RoHS
Compliant
1
Listed for use on 75°C insulated conductors.
APPLICATION/WIRING DIAGRAM
* Terminal block may extend up to 1/8” over the height dimensions shown.
ORDERING INFORMATION
2.5" *
(64 mm)
2.1"
(54 mm)
3.5"
(89 mm)
2.9"
(74 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
1.2"
(31 mm)
Removable Mounting Bracket
0.7"
(18 mm)
0.5"
(13 mm)
2.1"
(54 mm)
1.0" *
(26 mm)
0.6"
(16 mm)
ACCESSORIES
DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)
AH01
AV01
AV02
HQ0002067.A 09121
Fan or Pump
CONTROL
DI
Motor
VERIS IND
USTRIES
Po
rtland, Or
egon 97223
1-800-354-
8556
Hawkeye
®
614
VFD
BYPASS DEVICE
(if used)
NOTE: The H614 is not intended
for use in staged pump or variable
inlet vane applications.
NOTE: (Optional) For added
sensitivity in detecting amperage
changes, use H614 devices on all
three phases of the VFD (see “How
It Works” for details).
E150462