HOW IT WORKS

The H614 is designed for HVAC fan and blower systems, as well as some pumping
systems involving consistent viscosity liquids. If an H614 is installed on one phase
of the VFD, it detects changes in that phase that result from the VFD compensating
for changes elsewhere in the system. Alternatively, for increased sensitivity, H614s
can be used on all three phases for immediate detection of phase balance changes
anywhere in the system.

During setup, the H614 automatically determines the normal amperage and
frequency profile and stores it in nonvolatile memory. Then the microprocessor
monitors for amperage changes greater than ±20% of this learned curve.

Sensor Mode

Status LED Blink Pattern

Learning Mode (first 15 sec of operation after

frequency stabilizes)

Alternating Red/Green (1 per sec.)

On/Off Status only; Learn mode incomplete.

VFD system does not meet abnormal condition

detection criteria

Green blink (5 times per sec. after

15 sec of stable frequency)

Status OK

Green blink (1 per sec.)

Alarm

Red blink (1 per sec.)

MODEL AMPERAGE

RANGE

FREQUENCY

RANGE

STATUS OUTPUT NOMINAL TRIP POINT

TARGET RANGE

HOUSING STATUS

LED

UL

CE

RoHS

H614

1.5 - 150A

12 - 115 Hz

N.O. 1.0A@30VAC/DC

±20%

Split-core

n

n

1

n

n

DIMENSIONAL DRAWING

RoHS

Compliant

1

Listed for use on 75°C insulated conductors.

APPLICATION/WIRING DIAGRAM

* Terminal block may extend up to 1/8” over the height dimensions shown.

ORDERING INFORMATION

2.5" *

(64 mm)

2.1"

(54 mm)

3.5"

(89 mm)

2.9"

(74 mm)

0.4” x 0.2”

(10 mm x 5 mm)

Slot (2x)

1.2"

(31 mm)

Removable Mounting Bracket

0.7"

(18 mm)

0.5"

(13 mm)

2.1"

(54 mm)

1.0" *

(26 mm)

0.6"

(16 mm)

ACCESSORIES

DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)

AH01

AV01

AV02

HQ0002067.A 09121

Fan or Pump

CONTROL

DI

Motor

VERIS IND

USTRIES

Po

rtland, Or

egon 97223

1-800-354-

8556

Hawkeye

®

614

VFD

BYPASS DEVICE

(if used)

NOTE: The H614 is not intended
for use in staged pump or variable
inlet vane applications.

NOTE: (Optional) For added
sensitivity in detecting amperage
changes, use H614 devices on all
three phases of the VFD (see “How
It Works” for details).

E150462