Veris Industries H84xxVBS SERIES Datasheet User Manual
Power meter for voltage-mode cts, Po wer/ener g y monit oring

p
o
wer/ener
g
y monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Maximize System Efficiency and
Gain Precise Power Quality with
1% Energy and Power Accuracy
Power Meter for Voltage-Mode CTs
DESCRIPTION
The H84xxV, H84xxVB, and H84xxVBS Series digital power meters deliver high
accuracy and high value at a competitive price.
Whether you are looking for a 1-phase pulse output meter to monitor kWh, or a
3-phase communicating meter to monitor THD, the H84xxV Series has the right
meter for you, in panel and wall mounting styles for your convenience.
The pulse output unit offers two pulse outputs. While kWh is standard, the second
pulse output provides a field-selectable choice between phase loss or kVARh.
The Modbus communications unit offers a choice between two data outputs, Full
Data Set (FDS) or Extended Data Set (EDS). Data points are listed on the next page.
APPLICATIONS
●
Energy management and performance contracting
●
Submetering for commercial tenants
●
Activity-based costing in commercial and industrial facilities
FEATURES
●
Revenue Grade measurements
●
Intuitive navigation with context-sensitive menus for easy use
●
Panel, wall, DIN rail mount...provide mounting flexibility
●
Digital power meters automatically detect and correct phase reversal,
eliminating the need to be concerned with CT load orientation...fast,
trouble-free installation
●
Real-time power monitoring via local display or through control/data
acquisition systems
●
Large, easy-to-read display
●
Multiple values displayed at the same time on an anti-glare display
featuring a green back-light
SPECIFICATIONS
Inputs:
Control Power
100 to 415 ± 10%VAC, 5VA, 45-60 Hz
DC
125 to 250VDC ± 20%VDC, 3W *
Voltage Input
UL: 600VAC; CE: 300VAC (L-N)
Current Input
CT Scaling
Primary: Adjustable from 5A to 32,767A
Measurement Input Range
1V RMS full scale (+20% over-range)
Accuracy:
Current and Voltage 0.5%
Power
ANSI C12.16, 1%
Measurement - True RMS
True RMS up to 15th harmonic, 3-phase AC System
Outputs:
Pulse Output #1
(kWH ) N.O. Static Output (240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation
Pulse Output #2 (H8463V/VB/VBS)
(Phase Loss or kVARh) N.C. Static Output(240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation
Mechanical:
Weight
H84xxV: 0.8 lbs; H84xxVB: 6.35 lbs; H84xxVBS: 9.15 lbs
Protection Class
V: IP40 front, IP30 back; VB: NEMA 1, IP40
Environmental:
Operating Temperature Range
Meter: 0° to 60°C (32° to 140°F); Display: -10° to 50°C (14° to 122°F)
Storage Temperature Range
Meter and Display: -40°C to 85°C (-40° to 185°F)
Humidity Range
0-95% noncondensing
Agency Approvals
UL508; ANSI C22.2, Cat. III, Pollution Degree 2, for distribution systems up to 347VAC (L-N)/600VAC (L-L);
CE per IEC61010, Cat. III, Pollution Degree 2, for distribution systems up to 300VAC (L-N)/480VAC (L-L)
*For control voltages >415VAC to 600VAC order H84xxVBS
H84xx
H84xxVBS
Year
Warranty
5
H84xxV, H84xxVB, & H84xxVBS SERIES
BACnet
connec
tivity
via new
E8950
Gateway
HQ0001713.B 01131