Veris Industries H704 SERIES Datasheet User Manual
Branch current monitor, solid-core, Monitor current on every breaker, H704 series

p
o
wer/ener
g
y monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
FEATURES
●
Up to 63 H704s can be networked on one Modbus RS-485 drop...simplified wiring
●
Reports current consumed on each circuit in the panel board...one product covers
multiple points
●
3/4 or 1 inch on center current sensors accommodate standard breakers...easy
installation
●
Provides Modbus registers for current limit warnings and alarms...prevents
breaker trips
●
Integrates with available network display for local indication
●
Built-in ability to set the orientation and numbering of the circuits
DESCRIPTION
The H704 Series branch circuit current monitoring system provides a cost-effective
solution for electrical load management, making it ideally suited for applications
where load capacity requirements are dynamic, such as the data storage industry,
lighting panels, etc.
The H704 monitors the current draw of each breaker in a panelboard. The
accumulated information can be transmitted to a Modbus host and/or viewed on
an optional local display via an RS-485 network. Data updates occur approximately
once per second to provide timely preventative maintenance information. As a circuit
approaches capacity, warning and alarm levels trigger (see graph, facing page).
Additional capacity can then be added, or loads balanced, to prevent costly downtime
from overloaded circuits and unexpected breaker trips.
APPLICATIONS
●
Retrofitting panelboards
●
Cost allocation
●
Protecting against overload
●
Managing and balancing loads
●
Lighting circuits
Monitor Current on Every
Breaker
Branch Current Monitor,
Solid-Core
SPECIFICATIONS
Inputs:
Input Power
120VAC (+10/-25%) line-to-neutral, 50/60Hz; (208/230VAC for H704-42E)
Frequency
50/60Hz
Accuracy:
Accuracy
±2% of reading from 5A to 50A
Sampling Frequency
1280 Hz
Update Rate
1.2 sec
Outputs:
Type
Modbus® RTU
Connection
DIP-switch selectable 2-wire or 4-wire
Address
DIP-switch selectable address 1 to 247
Baud Rate
DIP-switch selectable 2400, 4800, 9600, 19200
Parity
DIP-switch selectable NONE,ODD,EVEN
Communication Format
8 data-bits, 1 start-bit, 1 stop-bit
Mechanical:
Connection to Conductor
Solid-core toroid
†
Number of Channels
up to 42
Environmental:
Operating Temperature Range
0° to 60°C (32° to 140°F) (<95%RH, non-condensing)
Storage Temperature Range
-40° to 70°C (-40° to 158°F)
†
Do not apply 300V Class current transformers to circuits having a line-to-neutral voltage greater than 300V, unless adequate additional insulation
is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury
caused by products operated on circuits above their published ratings.
Year
Warranty
5
H704
H704 SERIES
HQ0001912.A 01121
H704 Series transducers are sold as an open device.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.