opEration

The H722LC is a current transducer that senses current (amperage) in any of three
field-selectable ranges: 0-10, 0-20, or 0-40 amperes. These ranges represent the
maximum current that can be applied to the monitored conductor. The H722LC
transforms the monitored current into a 0-5VDC output suitable for connection to
building controllers or other appropriate data acquisition equipment. The H722LC
requires no external power to generate its output.

notEs

troublEshooting

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

• Controller must be
programmed to account
for the extra turns. e.g., if
four turns pass through
the sensor (as shown) the
normal controller reading
must be divided by 4.

DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H681x-5A CT

> 40A (H722LC max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of

turns through the sensing window using the following

formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps

e.g. : 30A ÷ 4 Turns = 7.5 Amps max. in monitored conductor

Failure to follow these instructions can result in overheating

and permanent equipment damage.

Problem

Solution

No Reading at Controller

• Confirm measured current is within the selected

range on the product.

• Check polarity of sensor output connections.

SENSED AMPS

Selected Range*

0 VDC

0A

5 VDC

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

calibration/scaling

Set the amperage range selector switch to a level appropriate for your load. The
H723LC is available with three choices, 0-10, 0-20, or 0-40 Amps.

DDC

CONTROLLER

AI

COMM

0-5VDC Input

CAUTION: Consult
instructions prior
to installation

!

Use min. 75º C insulated conductor

ig20

AMPERAGE

RANGE

40
20
10

OUTPUT
0-10VDC

+ –

+

Self-Powered Output

Scale the output as shown below.

Wiring

Amperage Range
Selector Switch