INSTALLATION GUIDE

H909HV

OPERATION

The H909HV is a current-sensitive switching device that monitors current (amperage)
in the conductor passing through it. A change in amperage in the monitored
conductor which crosses the switch (trip point) threshold plus the hysteresis value
will cause the resistance of the status output to change state, similar to the action of
a mechanical switch. In this model, the trip point is adjustable through the action of
a twenty (20) turn potentiometer (see the CALIBRATION section). The status output is
suitable for connection to building controllers or other appropriate data acquisition
equipment operating at up to 250 volts. The H909HV requires no external power
supply to generate its output.

The H909HV housing offers unprecedented mounting flexibility. The mounting
bracket can be attached in three different places. Additionally, the bracket is
compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.

NOTES

TROUBLESHOOTING

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.

4x

1A

DANGER: 5A CTs can present hazardous voltages.

Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H68xx‑5A CT

240A

300A:

5A

4A

> 135A (Sensor max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) when added safety is desired for a low current
load on a high current source.

Problem

Solution

No Reading at Controller

• Check sensor calibration (see above)
• Check for control voltage at sensor (250V)
• Check for amperage in monitored conductor (> 2.5A)
• Assure that sensor core mating surfaces are clean and

that the core clamp is completely closed

Setpoint screw has no stops

The setpoint screw has a slip-clutch at both ends of its

travel to avoid damage. Twenty turns CCW will reset

the sensor to be most sensitive. Repeat calibration

above.

Both LEDs are lit

Setpoint screw is too far clockwise. See solution above.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of turns

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor

• Failure to follow these instructions can result in overheating

and permanent equipment damage.

CALIBRATION

Program controller to account
for the extra turns. e.g., if four
turns pass through the sensor
(as shown) divide the normal
controller reading by 4.

< 2.5 A (Sensor Min.)

A. To monitor under-current (belt loss, coupling shear, status)

A

OK!

!

1. Turn setpoint screw
counter-clockwise until
Status OPEN LED turns ON.

2. Slowly turn the screw clockwise until the Status CLOSED LED just turns ON.

3. Turn the screw
an additional 1/4
turn clockwise for
operational margin.

B. To monitor over-current (mechanical problems, seized impeller)

A

OK!

!

3. Turn the setpoint
screw an additional
1/4 turn counter-
clockwise for
operational margin.

1. Turn setpoint screw clockwise until
Status CLOSED LED turns ON.

2. Slowly turn the setpoint screw counter-clockwise until the Status OPEN LED just
turns ON.

OK!

STATUS

OK!

STATUS

Setpoint

Status

Open

STOP

Setpoint

Status

Closed

STOP

+

Setpoint

Status

Closed

STOP

+

1/4

Setpoint

Before beginning calibration, establish normal load conditions.

OK!

A

OK!

Then choose either A or B below.

1/4

Setpoint

Setpoint

Status

Open

STOP