Veris Industries H909HV Install User Manual
H909hv, 909hv, Notice
TM
CURRENT MONITORING
INSTALLATION GUIDE
Z205454-0E
PAGE 1
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Split-Core Current Switch, Adjustable Trip Point
with 250VAC/DC Output
Installer’s Specifications
Amperage Range
2.5 to 135A Continuous
Sensor Power
Induced from monitored conductor
Max. Current 200A
Frequency
50/60Hz
Switch Output
Max. current: 1A; max. voltage: 250VAC/DC
Hysteresis
10% of setpoint, typical
Insulation Class
300V (CE); 600VAC RMS
Temperature Range
-15° to 60° C (-5° to 140° F)
Humidity Range
10-90% RH non-condensing
Output Resistance - Off-State
0 (open switch represents 1+ MΩ of resistance)
Terminal Block Maximum Wire Size
14 AWG
Terminal Block Torque (nominal)
4 in-lbs (0.45 N-m)
For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001, Installation
Category III or equivalent.
The product design provides for basic insulation only.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
WIRING EXAMPLE
H909HV
TM
909HV
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
INSTALLATION
Disconnect and lock out power to the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state
contact).
4. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
Removable Mounting Bracket
Self-gripping
Iris
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
2.8”
(70 mm)
Ø = 0.3”
(8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted
on three sides for added
installation flexibility.
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan‑
dard DIN rail.
Fan or Pump
CONTACTOR
MOTOR
Insulated Conductor
DDC CONTROLLER
DI