Veris Industries CWV SERIES Datasheet User Manual
Wall co2 sensors, dual analog outputs, Cwv series, Air qu alit y
![background image](/manuals/259791/1/background.png)
AIR QU
ALIT
Y
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Wall CO2 Sensors,
Dual Analog Outputs
Dual Analog Outputs, Switchable
0-3/5/10 Volt/4-20 mA Output
DESCRIPTION
The CWV Series is a non-dispersive infrared sensor designed for measuring CO2
concentration in office and living spaces. Its 2000 ppm measurement range makes it
an ideal solution for meeting ASHRAE and other ventilation control standards.
The CWV Series features multiple output options, microprocessor-based digital
technology, and a unique self-calibration algorithm which improves long-term
stability and accuracy.
APPLICATIONS
●
Controlling HVAC in response to occupancy – save energy by providing
ventilation only as required
●
Improving tenant comfort
●
Schools, museums, airports, commercial buildings, etc.
●
OEM applications
●
Home automation
●
Big-box retail
●
Restaurants
●
C-Stores
●
Bid/Spec market
SPECIFICATIONS
Input Voltage
20 to 30VDC, 24VAC
Analog Output #1
4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)
Analog Output #2
4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)
Sensor Current Draw
200mA Maximum
Operating Humidity Range
0-95% RH noncondensing
Operating Temperature Range
0° to 50°C (32° to 122°F)
Housing Material
High impact ABS plastic
CO2 Transmitter:
Sensor Type
Non-dispersive infrared (NDIR), diffusion sampling
Measurement Range
0-2000 ppm
Accuracy
±40 ppm ±5.5% of measured value
Repeatability
±30 ppm ±4.5% of measured value
Response Time
<60 seconds for 90% step change
Relay Contacts
1A@30VDC, resistive; 30W max.
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).
Year
Warranty
1
CWV
FEATURES
●
Microprocessor-based design reduces long-term drift and
calibration requirements
●
Non-dispersive infrared technology (NDIR) repeatable to ±30 ppm ± 4.5% of
measured value...high accuracy measurements
●
Innovative self-calibration algorithm...easy to maintain
●
5-year calibration interval (recommended)
●
Low ambient sensitivity
●
Improve comfort and facilitate compliance with ASHRAE 62.1 standard
for air quality
●
Demand control ventilation provides reduction in energy costs...helps with
green branding initiatives
●
Dual analog outputs...added user convenience
●
LED indication for power and error detection...reduces
time spent troubleshooting
●
Switchable 0-3/5/10V output...increased flexibility
●
US & European mounting holes...installation flexibility
●
Field calibratable...reduce costly downtime
●
4-20mA and voltage outputs in one unit...greater versatility
CWV SERIES
HQ0001742.B 01131