Installation Guide

Current Monitoring

H706

TM

Before beginning calibration, establish normal load conditions. Then choose either A or B below.

A. To monitor under-current (belt loss, coupling shear, status)

1. Turn setpoint screw clockwise

until Status Closed LED turns

on.

Status

Closed

Status

Open

Setpoint

2. Slowly turn the screw counter

clockwise until the Status

Open LED turns on.

Status

Closed

Status

Open

Setpoint

3. Turn the screw an additional

¼ turn counter clockwise for

operational margin.

¼

Status

Closed

Status

Open

Setpoint

B. To monitor over-current (mechanical problems, seized impeller)

1. Turn setpoint screw counter

clockwise until Status Open

LED turns on.

Status

Closed

Status

Open

Setpoint

2. Slowly turn the setpoint screw

clockwise until the Status

Closed LED just turns on.

Status

Closed

Status

Open

Setpoint

3. Turn the setpoint screw an

additional ¼ turn clockwise for

operational margin.

¼

Status

Closed

Status

Open

Setpoint

Calibration

Troubleshooting

Problem

Solution

No Reading at Controller

• Check sensor calibration (see above)
• Check for control power at sensor (5VDC• Check for amperage in monitored conductor (>1A)
• Verify correct polarity

Setpoint screw has no stops

• The setpoint screw has a slip-clutch at both ends of its travel to avoid damage. Twenty turns CCW will reset

the sensor to be most sensitive. Repeat calibration above.

Both LEDs are lit

Unit is out of calibration. Turn screw 20 turns CCW and recalibrate.