Veris Industries HO SerieS Install User Manual
Ho series, Notice, Digital rh and rh/t transmitters
Z201382-0X
PAGE 1
©2011 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]
02112
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
Digital RH and RH/T Transmitters
Installer’s Specifications
HS Element
Digitally profiled thin-film capacitive (32-bit mathematics)
U.S.
Patent No. 5,844,138
Accuracy @ 25°C from 10-80% RH*
2%, 3%, or 5% (specify);
Multi-point
calibration, NIST traceable
Reset Rate**
24 hours
Stability
±1% @ 20°C (68°F) annually, for two years
Operating Humidity Range
0 to 100% RH
Operating Temperature Range
-40° to 50°C (-40° to 122°F)
Hysteresis
1.5% typical
Linearity
Included in Accuracy spec.
Temperature Coefficient
±0.1% RH/°C above or below 25°C (typical)
Analog Output
4-20mA version: 2-wire, polarity insensitive (clipped and capped);
0-5V/0-10V
versions: 3 wire; observe polarity
Scaling
0–100% RH
Input Power***
4-20mA version: loop powered 12-30VDC only, 30mA max.;
0-5V/0-10V
versions: 12-30VDC/24VDC, 15mA max.
Optional Temperature Transmitter Output
Digital, 4-20mA (clipped and capped)
or
0-5V/0-10V output; accuracy ±1.3°C (±2.3°F) typical
EMC Conformance - CE Option
EN50081-1, EN 50082-1, EN 61000-4-4, EN 61000-4-5,
EN61000-4-3,
ENV 50204, EN61000-4-6
* Specified accuracy with 24VDC supplied power with rising humidity.
** Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
*** One side of transformer secondary is connected to signal common. Isolation transformer or
dedicated power supply may be required.
RTD Thermistors are not compenstated for internal heating of product
To conform to EMC standards, shielded cabling and technical information is available from factory
upon request or is available on our website: www.veris.com
HO SerieS
HO SerieS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
Available
DIMENSIONS
T = Temp
X = No Temp
(Stop here)
US or EU
Temp.
Sensor Type
Accuracy
NIST
S = Standard
C = CE
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/˚C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
Output
M = 4-20mA
V = 0-5V/0-10VDC
2 = 2%
3 = 3%
5 = 5%
HO
Sensor Type Range
Temp Cert
Blank = None
1 =1pt Cal
2 = 2pt Cal
OPTION
Humidity Transmitter Combination Humidity RTD/Thermistor Combination
Blank = None
1 =1pt Cal
2 = 2pt Cal
A
= Transmitter
N = NIST
X = None
Temp Cert
OPTION
1 = -40° to 50°C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)
2.3"
(58 mm)
4.6"
(116 mm)
0.7"
(18 mm)
12.2"
(310 mm)
2.8"
(72 mm)
2.7"
(69 mm)
QUICK INSTALL
1. Choose an outdoor location in a sheltered area, out of direct sunlight.
2. Mount unit with probe pointing down. Unit may be suspended by conduit. Do not
obstruct vent openings.
3. Wire probe (see Wiring section). Leave wires at factory length to allow for a service
loop (to remove sensor from junction box for service without disturbing the
conduit).
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.