beautypg.com

Caution, Installation guide, Operation – Veris Industries H923 Install User Manual

Page 2: Scaling, Troubleshooting, Wiring, H923

background image

H923

Z202365-0H

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

OPERATION

The H923 is a current transducer that senses current (amperage) in any of three
field-selectable ranges; 0-to-20, 0-to-100, or 0-to-150 Amps. These ranges represent
the maximum current that can be applied to the monitored conductor. The H923
transforms the monitored current into a 0 to 10 VDC output suitable for connection
to building controllers or other appropriate data acquisition equipment. The H923
requires no external power supply to generate its output.

The H923 housing offers unprecedented mounting flexibility. The mounting bracket
can be attached in three different places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.

NOTES

For load currents greater than sensor maximum rating:

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.

4x

1A

DANGER: 5A CTs can present hazardous voltages.

Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H68xx-5A CT

240A

300A:

5A

4A

> 150A (Sensor max.)

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of turns

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor

• Failure to follow these instructions can result in overheating

and permanent equipment damage.

Program the controller to
account for the extra turns,
e.g., if four turns pass through
the sensor (as shown) then
divide the normal controller
reading by 4.

< 1.5 A (Sensor Min.)

SCALING

1. Set range switch.

2. Scale controller

software to match
selected output.

20

100

150

Amperage Range
Selector Switch

20

100

150

AMPERAGE RANGE

AMPERAGE RANGE

SENSOR OUTPUT

Selected Range

0V

0A

10V

SENSED AMPS

TROUBLESHOOTING

Problem

Solution

No Reading at Controller

• Check polarity of sensor output connections
• Check for output voltage at sensor
• Check for amperage in monitored conductor
• Assure that sensor core mating surfaces are clean and

that the core clamp is completely closed

DDC

CONTROLLER

AI

COMM

0-10VDC Input +

Self-Powered Output

20

100

150

OUTPUT
0-10VDC

AMPERAGE RANGE

WIRING