beautypg.com

Installation guide, Installation, Veris industries – Veris Industries TWS SERIES Install User Manual

Page 2: Tws series

background image

VERIS INDUSTRIES

inStallation GUiDe

tWS SerieS

Z204455-0D

PAGE 2

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

06101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

RH

YES

AMP

VOLT

NO

RUN

CAL

Minus

Plus

Enter

+

1. Remove the cover by pressing the tab at the top of the sensor while pulling

outward from the top of the cover.

5. Mount the backplate onto the wall using the screws provided.

6. Wire the backplate.

3. Punch out openings in the backplate.

7. Install and configure the sensor.

8. Install the cover and snap into place.

correct

incorrect

4. Position the sensor vertically on the wall, 4 1/2 feet above the floor.

WARNING: Output select must be
correct before applying power.

Five screwholes available; use a mini-
mum of two for secure mounting.

2. Remove the backplate by unfastening the sensor from the bottom of the backplate

and pivoting the sensor outward.

installation

Output (3-Wire, 0-10V, 4-20mA)

POWER SUPPLY

24 VAC/DC

CONTROL SYSTEM

COMMON

TEMP INPUT

TEMP SETPOINT INPUT

THERMISTOR

PWR COMMON

TEMP OUT

TEMP SETPOINT

RTD

RTD

RH

SENSOR

TEMP

SENSOR

AMP

VOLT

YES

RUN

CAL

NO

TEMP

Minus

Plus

Enter

+

RUN/CAL JUMPER:
CAL Mode - allows full access to all
features.
RUN Mode - allows access to setpoint
ONLY.

TEMP YES/NO JUMPER:
YES - allows user to change setpoint
(in thermostat mode)
NO - user can NOT change setpoint
(in thermostat mode)