INSTALLATION GUIDE

4. Configure the output switch, jumpers, and range.

A. Use the switch to select voltage (V) or current (mA) mode.

B. Jumpers:

Jumper JP4: select 0-10 V or 0-5 V output span (voltage mode only).

Jumper JP5: select bidirectional or unidirectional mode.

Jumper JP7: select inches W.C. or Pascal scale

Jumper JP8: select fast or standard response time.

C. Align the arrow (not the slot) on the rotary dial to the desired full-scale range.
LCD models momentarily indicate the selected range.

Range Selection Guide

PX01

PX02

Rotary

Switch

Position

Inches

W.C.

Pascal

Inches

W.C.

Pascal

0

0.1

25

1

250

1

0.25

50

1

250

2

0.5

100

1

250

3

1

250

1

250

4

1

250

2.5

0.5 kPa

5

1

250

5

1 kPa

6

1

250

10

2.5 kPa

7

1

250

10

2.5 kPa

5. Secure the panel and reconnect power.