INSTALLATION GUIDE
4. Configure the output switch, jumpers, and range.
A. Use the switch to select voltage (V) or current (mA) mode.
B. Jumpers:
Jumper JP4: select 0-10 V or 0-5 V output span (voltage mode only).
Jumper JP5: select bidirectional or unidirectional mode.
Jumper JP7: select inches W.C. or Pascal scale
Jumper JP8: select fast or standard response time.
C. Align the arrow (not the slot) on the rotary dial to the desired full-scale range.
LCD models momentarily indicate the selected range.
Range Selection Guide
PX01
PX02
Rotary
Switch
Position
Inches
W.C.
Pascal
Inches
W.C.
Pascal
0
0.1
25
1
250
1
0.25
50
1
250
2
0.5
100
1
250
3
1
250
1
250
4
1
250
2.5
0.5 kPa
5
1
250
5
1 kPa
6
1
250
10
2.5 kPa
7
1
250
10
2.5 kPa
5. Secure the panel and reconnect power.