beautypg.com

Charging – Power-Sonic Sealed Lead Acid Batteries - Technical Manual User Manual

Page 20

background image

Charging

Charging in Parallel

Power-Sonic batteries may be used in parallel with one or more batteries of equal voltage.

When connected in parallel, the current from a charger will tend to divide almost equally between the batteries. No

special matching of batteries is required. If the batteries of unequal capacity are connected in parallel, the current will

tend to divide between the batteries in the ratio of capacities (actually, internal resistances).

When charging batteries in parallel, where different ratios of charge are to be expected, it is best to make provisions to

assure that the currents will not vary too much between batteries.

Temperature Compensation

Power-Sonic batteries perform well both at low and high temperatures. At low temperatures, however, charge efficiency is

reduced; at temperatures above 45°C (113°F), charge efficiency increases so rapidly that there is a danger of thermal

runaway if temperature compensation is not precise.

The effect of temperature on charge voltage is less critical in float applications than in cyclic use, where relatively high

charge currents are applied for the purpose of short recharge times.

Temperature effects should definitely be considered when designing or selecting a charging system. Temperature

compensation is desirable in the charging circuit, especially when operating outside the range of 5°C to 35°C

(41°F to 95°F). The temperature coefficient is -2mV/cell/ºC below 20°C (68°F) in float use and -6mV/cell/ ºC below

20°C in cyclic use. For higher temperatures the charge voltage should be correspondingly decreased.

Top Charging

All battery lose capacity through self-discharge, it is recommended that a “top up charge” be applied to any battery that

has been stored for a long period of time, prior to putting the battery into service.

To successfully top charge a battery stored for more than 12 months, the open circuit voltage must be higher than 2.0

volts per cell, in this case, always confirm open circuit voltage prior to attempting top up charging.

Ambient Charge Voltage Per Cell

Temperature

Cyclic Use (V)

Float Use (V)

-40°C (-40°F)

2.85 – 2.95

2.38 – 2.43

-20°C (-4°F)

2.67 – 2.77

2.34 – 2.39

-10°C (14°F)

2.61 – 2.71

2.32 – 2.37

0°C (32°F)

2.55 – 2.65

2.30 – 2.35

10°C (50°F)

2.49 – 2.59

2.28 – 2.33

20°C (68°F)

2.43 – 2.53

2.26 – 2.31

25°C (77°F)

2.40 – 2.50

2.25 – 2.30

30°C (86°F)

2.37 – 2.47

2.24 – 2.29

40°C (104°F)

2.31 – 2.41

2.22 – 2.27

50°C (122°F)

2.25 – 2.35

2.20 – 2.25

Table : Recommended charge voltages for different temperatures.