beautypg.com

Power-Sonic PSX12-3.5 User Manual

Psx series, Vrla 6yr design life at 20°c)

background image

PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-3.5 12V 3.5AH

Nominal Voltage

Nominal Capacity

12V

3.5 AH

Dimension

Length

Width

Container Height

Total Height (with terminal)

Weight

Standard Terminal

F1

Approx 1.35kg

134

67

60

66

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

C

on

s

tant V

oltag

e

C

h

a

rge

Recommended Charge
Current less than 0.87A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

4.75

6.35

3.2

0.8

F1

Approx 45.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 - 02/13

-

(VRLA 6yr Design Life at 20°C)

60

2

66

2

+

-

67 2

134 2

Power

Rating

1hr Rate(1.67V/cell)

3hr Rate(1.67V/cell)

15min Rate(1.67V/cell)

27.12 Watts

11.04 Watts

70.98 Watts

Constant Power Discharge Characteristics Unit: W atts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

F.V(V/cell)

15min

1H

3H

1.85

4.91

2.03

0.81

1.80

5.34

2.14

0.87

1.75

5.85

2.24

0.89

1.70

6.24

2.31

0.92

1.67

6.63

2.39

0.95

1.60

6.96

2.47

0.98

F.V(V/cell)

15min

1H

3H

1.85

9.19

3.91

1.59

1.80

9.89

4.10

1.71

1.75

10.67

4.28

1.73

1.70

11.25

4.40

1.78

1.67

11.83

4.52

1.84

1.60

12.22

4.65

1.89

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

Table of contents