Dell UPS 10000R User Manual
Page 19

17
Installation and Startup
|
Connecting the Equipment
To install the UPS:
1
If you plan to use Dell MUMC and Dell ULNM software, establish communication in one of the
following ways:
S
using the Dell Network Management Card (if installed)
S
using the supplied cable to connect your computer to the USB port
NOTE:
For more information about communication options, refer to the Dell Online Rack UPS 10 kW User's
Guide.
2
If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the
ground cable (not supplied) to the ground bonding screw. See “UPS Rear Panels” on page 24 for
the location of the ground bonding screw for each of the three models.
3
If an emergency power-off (disconnect) switch is required by local codes, refer to “Installing
Remote Emergency Power-off” in the Dell Online Rack UPS 10 kW User's Guide.
4
If you are installing an optional EBM, refer to the Dell Online Rack EBM 10 kW Getting Started
Guide for installation instructions.
CAUTION:
If the UPS is stored or used without an EBM, the battery connector cover on the rear panel of the
UPS must be installed as a safety precaution.
5
Plug the equipment to be protected into the UPS output receptacles, but do not turn on the
protected equipment.
6
Make any necessary provisions for cord retention and strain relief.
NOTE:
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.