Table 2: ratings cooling/gas heating – York DNH018 User Manual
Page 7
036-21233-002-A-0903
Unitary Products Group
7
TABLE 2: RATINGS COOLING/GAS HEATING
MODEL
DNH
NET COOLING CAPACITY
1
SOUND
RATING
(dbels)
2
GAS HEAT CAPACITY / EFFICIENCIES
MBH
SEER
3
INPUT
(MBH)
OUTPUT
(MBH)
AFUE
4
(%)
NUMBER OF
BURNERS
TEMP.
RISE
(°F) RANGE
018N03606
17.4
12.0
80
45
36
80.2
2
25 - 55
024N03606
23.8
12.4
81
45
36
80.2
2
25 - 55
024N05606
23.8
12.4
81
70
56
80.2
3
30 - 60
030N03606
28.0
12.0
80
45
36
80.2
2
25 - 55
030N03625
28.0
12.0
80
45
36
80.2
2
25 - 55
030N03646
28.0
12.0
80
45
36
80.2
2
25 - 55
030N05606
28.0
12.0
80
70
56
80.2
3
30 - 60
030N05625
28.0
12.0
80
70
56
80.2
3
30 - 60
030N05646
28.0
12.0
80
70
56
80.2
3
30 - 60
036N03606
36.0
12.0
81
45
36
80.4
2
25 - 55
036N03625
36.0
12.0
81
45
36
80.4
2
25 - 55
036N03646
36.0
12.0
81
45
36
80.4
2
25 - 55
036N03658
36.0
12.0
81
45
36
80.4
2
25 - 55
036N05606
36.0
12.0
81
70
56
80.2
3
25 - 55
036N05625
36.0
12.0
81
70
56
80.2
3
25 - 55
036N05646
36.0
12.0
81
70
56
80.2
3
25 - 55
036N05658
36.0
12.0
81
70
56
80.2
3
25 - 55
036N07206
36.0
12.0
81
90
72
80.1
4
30 - 60
036N07225
36.0
12.0
81
90
72
80.1
4
30 - 60
036N07246
36.0
12.0
81
90
72
80.1
4
30 - 60
036N07258
36.0
12.0
81
90
72
80.1
4
30 - 60
042N06506
42.0
12.0
80
80
64
80.6
3
25 - 55
042N06525
42.0
12.0
80
80
64
80.6
3
25 - 55
042N06546
42.0
12.0
80
80
64
80.6
3
25 - 55
042N06558
42.0
12.0
80
80
64
80.6
3
25 - 55
042N09006
42.0
12.0
80
108
87
80.8
4
45 - 75
042N09025
42.0
12.0
80
108
87
80.8
4
45 - 75
042N09046
42.0
12.0
80
108
87
80.8
4
45 - 75
042N09058
42.0
12.0
80
108
87
80.8
4
45 - 75
048N06506
48.0
12.0
84
80
64
80.8
3
25 - 55
048N06525
48.0
12.0
84
80
64
80.8
3
25 - 55
048N06546
48.0
12.0
84
80
64
80.8
3
25 - 55
048N06558
48.0
12.0
84
80
64
80.8
3
25 - 55
048N09006
48.0
12.0
84
108
86
80.6
4
35 - 65
048N09025
48.0
12.0
84
108
86
80.6
4
35 - 65
048N09046
48.0
12.0
84
108
86
80.6
4
35 - 65
048N09058
48.0
12.0
84
108
86
80.6
4
35 - 65
048N11006
48.0
12.0
84
135
107
80.5
5
45 - 75
048N11025
48.0
12.0
84
135
107
80.5
5
45 - 75
048N11046
48.0
12.0
84
135
107
80.5
5
45 - 75
048N11058
48.0
12.0
84
135
107
80.5
5
45 - 75
060N06506
59.0
12.0
84
80
64
80.7
3
25 - 55
060N06525
59.0
12.0
84
80
64
80.7
3
25 - 55
060N06546
59.0
12.0
84
80
64
80.7
3
25 - 55
060N06558
59.0
11.0
84
80
64
80.7
3
25 - 55
060N09006
59.0
12.0
84
108
87
80.9
4
35 - 65
060N09025
59.0
12.0
84
108
87
80.9
4
35 - 65
060N09046
59.0
12.0
84
108
87
80.9
4
35 - 65
060N09058
59.0
11.0
84
108
87
80.9
4
35 - 65
060N11006
59.0
12.0
84
135
107
80.2
5
45 - 75
060N11025
59.0
12.0
84
135
107
80.2
5
45 - 75
060N11046
59.0
12.0
84
135
107
80.2
5
45 - 75
060N11058
59.0
11.0
84
135
107
80.2
5
45 - 75
1.
Net Cooling Capacity = ARI 210 standard rating conditions.
2.
(dbels) = ARI 270-95
3.
Seasonal Energy Efficiency Ration - the total cooling output in BTU’s during a normal annual usage period for cooling divided by
the total electric power input in watt-hours during the same period.
4.
AFUE = Annual Fuel Utilization Efficiency.