All sensible capacity – York DNH018 User Manual
Page 10
036-21233-002-A-0903
10
Unitary Products Group
TABLE 5: DNH030 COOLING CAPACITIES - 2-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
750 CFM
875 CFM
1,000 CFM
1,125 CFM
1,250 CFM
WB °F
WB °F
WB °F
WB °F
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85 °F
NET CAP.
MBH
27.2
26.8
24.1
24.0
28.5
28.1
25.3
25.2
29.8
29.4
26.4
26.4
29.4
29.0
26.1
26.0
29.0
28.6
25.7
25.6
TOTAL POWER
INPUT kW
2.35
2.34
2.32
2.32
2.40
2.39
2.37
2.36
2.44
2.43
2.41
2.40
2.52
2.51
2.49
2.48
2.60
2.59
2.57
2.56
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
17.3
22.2
24.1
24.0
19.4
24.9
25.3
25.2
21.6
27.6
26.4
26.4
22.4
28.1
26.1
26.0
23.3
28.6
25.7
25.6
83
15.1
20.1
23.0
23.9
16.9
22.4
24.7
25.1
18.7
24.7
26.4
26.4
19.1
25.1
26.1
26.0
19.6
25.6
25.7
25.6
80
13.0
17.9
20.8
21.7
14.4
19.8
23.0
24.0
15.8
21.7
25.2
26.3
15.8
21.8
25.3
26.0
15.8
21.8
25.4
25.6
77
10.9
15.8
18.7
19.6
11.8
17.3
20.5
21.5
12.8
18.8
22.3
23.4
12.5
18.5
22.0
22.7
12.1
18.1
21.6
21.9
74
8.7
13.7
16.5
17.5
9.3
14.8
18.0
19.0
9.9
15.9
19.4
20.5
9.1
15.1
18.7
19.3
8.4
14.4
17.9
18.2
71
-
11.5
14.4
15.3
-
12.3
15.5
16.5
-
13.0
16.5
17.6
-
11.8
15.3
16.0
-
10.7
14.2
14.4
68
-
9.4
12.3
13.2
-
9.7
12.9
13.9
-
10.1
13.6
14.7
-
8.5
12.0
12.7
-
6.9
10.5
10.7
95 °F
NET CAP.
MBH
24.0
23.0
21.1
20.5
26.6
25.5
23.3
22.7
29.2
28.0
25.6
24.9
29.1
27.9
25.5
24.8
29.0
27.7
25.4
24.7
TOTAL POWER
INPUT kW
2.56
2.54
2.50
2.50
2.60
2.58
2.54
2.54
2.65
2.63
2.58
2.58
2.74
2.71
2.67
2.67
2.82
2.80
2.76
2.75
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
16.1
20.7
21.1
20.5
18.8
24.2
23.3
22.7
21.6
27.6
25.6
24.9
22.6
27.7
25.5
24.8
23.7
27.7
25.4
24.7
83
14.0
18.5
21.1
20.5
16.3
21.6
23.3
22.7
18.7
24.7
25.6
24.9
19.3
25.4
25.5
24.8
19.9
26.2
25.4
24.7
80
11.8
16.4
19.2
18.6
13.8
19.1
22.4
21.7
15.7
21.8
25.6
24.7
16.0
22.1
25.5
24.7
16.2
22.4
25.4
24.7
77
9.7
14.3
17.1
16.5
11.3
16.6
19.9
19.1
12.8
18.9
22.7
21.8
12.7
18.8
22.2
21.4
12.5
18.7
21.7
21.0
74
7.6
12.1
15.0
14.3
8.7
14.0
17.4
16.6
9.9
16.0
19.8
18.9
9.3
15.5
18.9
18.1
8.8
15.0
17.9
17.2
71
-
10.0
12.8
12.2
-
11.5
14.8
14.1
-
13.1
16.9
16.0
-
12.2
15.5
14.8
-
11.3
14.2
13.5
68
-
7.8
10.7
10.0
-
9.0
12.3
11.6
-
10.1
13.9
13.1
-
8.8
12.2
11.4
-
7.5
10.5
9.8
105 °F
NET CAP.
MBH
22.8
20.8
19.4
19.0
25.1
22.9
21.4
20.9
27.4
25.0
23.3
22.8
27.5
25.1
23.4
22.9
27.7
25.2
23.5
23.0
TOTAL POWER
INPUT kW
2.76
2.72
2.68
2.68
2.81
2.77
2.73
2.72
2.85
2.81
2.77
2.77
2.94
2.90
2.86
2.85
3.03
2.99
2.95
2.94
S
e
n
s
ib
le
C
apaci
ty
MB
H
1
E
n
te
ring
Dry
Bu
lb
°
F
86
16.0
19.6
19.4
19.0
18.4
22.3
21.4
20.9
20.8
24.9
23.3
22.8
22.3
25.0
23.4
22.9
23.7
25.2
23.5
23.0
83
13.9
18.0
19.4
19.0
15.9
20.6
21.4
20.9
17.9
23.2
23.3
22.8
18.9
23.8
23.4
22.9
20.0
24.5
23.5
23.0
80
11.8
15.8
18.2
17.5
13.4
18.0
20.8
20.0
15.0
20.2
23.3
22.4
15.6
21.0
23.4
22.7
16.2
21.8
23.5
23.0
77
9.6
13.7
16.1
15.4
10.9
15.5
18.2
17.4
12.1
17.3
20.4
19.5
12.3
17.7
20.1
19.4
12.5
18.1
19.8
19.2
74
7.5
11.6
13.9
13.2
8.3
13.0
15.7
14.9
9.2
14.4
17.5
16.6
9.0
14.4
16.8
16.1
8.8
14.4
16.1
15.5
71
-
9.4
11.8
11.1
-
10.5
13.2
12.4
-
11.5
14.6
13.7
-
11.1
13.4
12.7
-
10.7
12.3
11.8
68
-
7.3
9.7
9.0
-
7.9
10.7
9.9
-
8.6
11.6
10.8
-
7.8
10.1
9.4
-
6.9
8.6
8.1
115 °F
NET CAP.
MBH
21.6
18.6
17.7
17.4
23.6
20.4
19.4
19.0
25.6
22.1
21.0
20.6
26.0
22.4
21.3
20.9
26.4
22.7
21.6
21.3
TOTAL POWER
INPUT kW
2.96
2.90
2.86
2.86
3.01
2.95
2.91
2.91
3.06
3.00
2.96
2.95
3.15
3.09
3.05
3.04
3.24
3.18
3.13
3.13
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
16.0
18.6
17.7
17.4
18.0
20.4
19.4
19.0
20.1
22.1
21.0
20.6
21.9
22.4
21.3
20.9
23.7
22.7
21.6
21.3
83
13.8
17.4
17.7
17.4
15.5
19.5
19.4
19.0
17.2
21.6
21.0
20.6
18.6
22.2
21.3
20.9
20.0
22.7
21.6
21.3
80
11.7
15.3
17.2
16.4
13.0
17.0
19.1
18.3
14.3
18.7
21.0
20.1
15.3
20.0
21.3
20.7
16.2
21.2
21.6
21.3
77
9.5
13.1
15.0
14.3
10.5
14.4
16.6
15.7
11.4
15.8
18.1
17.2
11.9
16.6
18.0
17.4
12.5
17.5
17.9
17.5
74
7.4
11.0
12.9
12.2
7.9
11.9
14.0
13.2
8.5
12.8
15.2
14.3
8.6
13.3
14.7
14.0
8.8
13.8
14.2
13.8
71
-
8.9
10.8
10.0
-
9.4
11.5
10.7
-
9.9
12.3
11.4
-
10.0
11.4
10.7
-
10.1
10.5
10.1
68
-
6.7
8.6
7.9
-
6.9
9.0
8.2
-
7.0
9.3
8.4
-
6.7
8.0
7.4
-
6.3
6.7
6.4
125 °F
NET CAP.
MBH
20.4
16.4
16.1
15.9
22.1
17.8
17.4
17.2
23.8
19.1
18.7
18.5
24.4
19.7
19.2
19.0
25.1
20.2
19.8
19.5
TOTAL POWER
INPUT kW
3.16
3.09
3.05
3.04
3.22
3.14
3.10
3.09
3.27
3.19
3.15
3.14
3.36
3.28
3.23
3.23
3.45
3.36
3.32
3.31
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
15.9
14.6
16.1
15.9
17.6
18.5
17.4
17.2
19.4
19.3
18.7
18.5
21.6
19.8
19.2
19.0
23.7
20.2
19.8
19.5
83
13.7
16.9
16.1
15.9
15.1
18.4
17.4
17.2
16.5
20.0
18.7
18.5
18.2
20.5
19.2
19.0
20.0
21.0
19.8
19.5
80
11.6
14.7
16.1
15.4
12.6
15.9
17.4
16.6
13.6
17.1
18.7
17.8
14.9
18.9
19.2
18.7
16.3
20.6
19.8
19.5
77
9.5
12.6
14.0
13.2
10.1
13.4
14.9
14.0
10.6
14.2
15.8
14.9
11.6
15.5
15.9
15.3
12.5
16.9
16.0
15.8
74
7.3
10.4
11.9
11.1
7.5
10.9
12.4
11.5
7.7
11.3
12.9
11.9
8.3
12.2
12.6
12.0
8.8
13.2
12.3
12.1
71
-
8.3
9.7
8.9
-
8.3
9.8
9.0
-
8.4
10.0
9.0
-
8.9
9.3
8.7
-
9.5
8.6
8.4
68
-
6.2
7.6
6.8
-
5.8
7.3
6.5
-
5.4
7.0
6.1
-
5.6
5.9
5.4
-
5.7
4.9
4.6
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY