Programmable thermostat only, Thermostat unit terminal strip, 24 volt transformer – York DNH018 User Manual

Page 19

background image

036-21233-002-A-0903

Unitary Products Group

19

FIGURE 2 - FIELD WIRING DIAGRAM CONTROL WIRING

FIGURE 3 - POWER WIRING FIELD DIAGRAM

TABLE 15: ADDITIONAL STATIC PRESSURE RESISTANCE 3-1/2 - 5 TON (DNH042 - 060)

1

DESCRIPTION

RESISTANCE, IWG

CFM

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

.07

.07

.08

.09

.09

ECONOMIZER

2

.02

.02

.02

.03

.03

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

.07

.08

.09

.10

.11

1.

Deduct these resistance values from the available external static pressure shown in Table 10, 11, 12, and 13

2.

The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

R

G

W

R

G

C

Y

Y

W

C

PROGRAMMABLE

THERMOSTAT ONLY

**

** = Minimum wire size of 18 AWG

wire should be used for all
field installed 24 volt wire.

THERMOSTAT

UNIT TERMINAL STRIP

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.

24 VOLT
TRANSFORMER

G R O U N D

L U G

R E F E R T O E L E C T R I C A L

D A T A T A B L E S T O S I Z E

T H E D I S C O N N E C T

F I E L D - S U P P L I E D

D I S C O N N E C T

C O N T A C T O R

F I E L D - S U P P L I E D

D I S C O N N E C T

C O N T A C T O R

G R O U N D

L U G

R E F E R T O E L E C T R I C A L

D A T A T A B L E S T O S I Z E

T H E D I S C O N N E C T

S I N G L E

P H A S E

P O W E R

S U P P L Y

T H R E E

P H A S E

P O W E R

S U P P L Y