036-21233-002-A-0903
Unitary Products Group
19
FIGURE 2 - FIELD WIRING DIAGRAM CONTROL WIRING
FIGURE 3 - POWER WIRING FIELD DIAGRAM
TABLE 15: ADDITIONAL STATIC PRESSURE RESISTANCE 3-1/2 - 5 TON (DNH042 - 060)
1
DESCRIPTION
RESISTANCE, IWG
CFM
1,100
1,200
1,300
1,400
1,500
1,600
1,700
1,800
1,900
2,000
WET EVAPORATOR COIL
.02
.03
.04
.05
.06
.07
.07
.08
.09
.09
ECONOMIZER
2
.02
.02
.02
.03
.03
.04
.04
.04
.05
.05
FILTER FRAME KIT
.04
.04
.05
.05
.06
.07
.08
.09
.10
.11
1.
Deduct these resistance values from the available external static pressure shown in Table 10, 11, 12, and 13
2.
The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
R
G
W
R
G
C
Y
Y
W
C
PROGRAMMABLE
THERMOSTAT ONLY
**
** = Minimum wire size of 18 AWG
wire should be used for all
field installed 24 volt wire.
THERMOSTAT
UNIT TERMINAL STRIP
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
24 VOLT
TRANSFORMER
G R O U N D
L U G
R E F E R T O E L E C T R I C A L
D A T A T A B L E S T O S I Z E
T H E D I S C O N N E C T
F I E L D - S U P P L I E D
D I S C O N N E C T
C O N T A C T O R
F I E L D - S U P P L I E D
D I S C O N N E C T
C O N T A C T O R
G R O U N D
L U G
R E F E R T O E L E C T R I C A L
D A T A T A B L E S T O S I Z E
T H E D I S C O N N E C T
S I N G L E
P H A S E
P O W E R
S U P P L Y
T H R E E
P H A S E
P O W E R
S U P P L Y