All sensible capacity – York DNH018 User Manual

Page 13

background image

036-21233-002-A-0903

Unitary Products Group

13

TABLE 8: DNH048 COOLING CAPACITIES - 4 TON

TEMPERATURE

OF AIR ON

CONDENSER COIL

AIR ON EVAPORATOR COIL

1,200 CFM

1,400 CFM

1,600 CFM

1,800 CFM

2,000 CFM

WB °F

WB °F

WB °F

WB °F

WB °F

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

85 °F

NET CAP.

MBH

50.8

47.4

43.1

42.8

52.8

49.3

44.8

44.5

54.8

51.2

46.5

46.2

55.5

51.9

47.1

46.8

56.2

52.5

47.7

47.4

TOTAL POWER

INPUT kW

4.01

3.98

4.02

3.98

4.06

4.03

4.07

4.03

4.11

4.08

4.12

4.08

4.24

4.20

4.25

4.20

4.36

4.33

4.37

4.33

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

30.9

38.8

43.1

42.8

34.6

43.3

44.8

44.5

38.2

47.7

46.5

46.2

41.0

50.1

47.1

46.8

43.8

52.5

47.7

47.4

83

27.5

35.4

41.8

41.8

30.5

39.2

44.2

44.0

33.6

43.0

46.5

46.2

35.7

45.6

47.1

46.8

37.8

48.3

47.7

47.4

80

24.1

32.0

38.4

38.4

26.5

35.2

42.3

42.2

28.9

38.4

46.1

46.1

30.4

40.3

46.9

46.7

31.8

42.3

47.7

47.4

77

20.7

28.6

35.0

35.0

22.4

31.1

38.2

38.2

24.2

33.7

41.4

41.4

25.1

35.0

41.6

41.4

25.9

36.3

41.7

41.4

74

17.2

25.1

31.6

31.6

18.4

27.1

34.2

34.2

19.6

29.0

36.8

36.8

19.7

29.7

36.3

36.1

19.9

30.4

35.8

35.5

71

-

21.7

28.1

28.1

-

23.0

30.1

30.1

-

24.4

32.1

32.1

-

24.4

31.0

30.8

-

24.4

29.8

29.5

68

-

18.3

24.7

24.7

-

19.0

26.1

26.1

-

19.7

27.4

27.4

-

19.1

25.6

25.5

-

18.4

23.9

23.6

95 °F

NET CAP.

MBH

48.7

44.9

40.8

40.7

50.8

46.8

42.6

42.4

52.9

48.8

44.4

44.2

54.8

50.5

46.0

45.8

56.7

52.3

47.5

47.4

TOTAL POWER

INPUT kW

4.34

4.34

4.38

4.35

4.39

4.39

4.43

4.40

4.44

4.43

4.47

4.44

4.56

4.56

4.60

4.57

4.68

4.68

4.72

4.69

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

29.7

36.7

40.8

40.7

33.7

41.6

42.6

42.4

37.8

46.5

44.4

44.2

41.5

49.4

46.0

45.8

45.2

52.3

47.5

47.4

83

26.2

33.3

38.8

38.9

29.7

37.6

41.6

41.6

33.1

41.9

44.4

44.2

36.2

45.7

46.0

45.8

39.2

49.5

47.5

47.4

80

22.8

29.8

35.3

35.5

25.6

33.5

39.7

39.9

28.4

37.2

44.0

44.2

30.8

40.4

45.8

45.8

33.3

43.5

47.5

47.4

77

19.4

26.4

31.9

32.1

21.6

29.5

35.6

35.8

23.8

32.5

39.4

39.6

25.5

35.1

40.5

40.5

27.3

37.6

41.6

41.4

74

13.0

23.0

28.5

28.6

17.5

25.6

31.6

31.8

19.1

27.9

34.7

34.9

20.2

29.7

35.2

35.2

21.4

31.6

35.6

35.4

71

-

19.6

25.1

25.2

-

21.4

27.6

27.7

-

23.2

30.0

30.2

-

24.4

29.8

29.8

-

25.7

29.6

29.5

68

-

16.2

21.6

21.8

-

17.3

23.5

23.7

-

18.5

25.4

25.6

-

19.1

24.5

24.5

-

19.7

23.7

23.5

105 °F

NET CAP.

MBH

47.9

43.1

39.9

39.9

48.9

44.0

40.8

40.7

49.9

44.9

41.6

41.5

51.4

46.3

42.8

42.8

52.8

47.6

44.1

44.0

TOTAL POWER

INPUT kW

4.78

4.78

4.81

4.78

4.83

4.83

4.86

4.83

4.88

4.88

4.91

4.88

5.01

5.01

5.04

5.01

5.14

5.14

5.17

5.14

S

e

n

s

ib

le

C

apaci

ty

MB

H

1

E

n

te

ring

Dry

Bu

lb

°

F

86

31.8

39.0

39.9

39.9

34.3

41.4

40.8

40.7

36.9

43.8

41.6

41.5

40.3

45.7

42.8

42.8

43.8

47.6

44.1

44.0

83

28.4

35.7

38.9

39.0

30.3

38.0

40.2

40.3

32.2

40.3

41.6

41.5

35.0

43.3

42.8

42.8

37.9

46.2

44.1

44.0

80

24.9

32.3

37.2

37.3

26.2

34.0

39.2

39.4

27.5

35.7

41.2

41.5

29.7

38.5

42.6

42.7

31.9

41.4

44.1

44.0

77

21.5

28.9

33.8

33.9

22.2

29.9

35.1

35.3

22.9

31.0

36.5

36.8

24.4

33.2

37.3

37.4

26.0

35.4

38.1

38.0

74

18.1

25.4

30.3

30.4

18.1

25.9

31.1

31.3

18.2

26.3

31.9

32.1

19.1

27.9

32.0

32.1

20.0

29.4

32.1

32.1

71

-

22.0

26.9

27.0

-

21.8

27.1

27.3

-

21.7

27.2

27.5

-

22.6

26.7

26.8

-

23.5

26.2

26.1

68

-

18.6

23.5

23.6

-

17.8

23.0

23.2

-

17.0

22.5

22.8

-

17.3

21.4

21.5

-

17.5

20.2

20.2

115 °F

NET CAP.

MBH

47.1

41.3

39.0

39.1

47.0

41.2

38.9

39.0

46.8

41.0

38.8

38.8

47.9

42.0

39.7

39.7

49.0

43.0

40.6

40.6

TOTAL POWER

INPUT kW

5.22

5.22

5.24

5.21

5.27

5.27

5.29

5.26

5.32

5.32

5.34

5.31

5.45

5.46

5.48

5.45

5.59

5.59

5.61

5.58

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

33.9

41.3

39.0

39.1

34.9

41.2

38.9

39.0

36.0

41.0

38.8

38.8

39.2

42.0

39.7

39.7

42.5

43.0

40.6

40.6

83

30.5

38.1

39.0

39.1

30.9

38.5

38.9

39.0

31.3

38.8

38.8

38.8

33.9

40.9

39.7

39.7

36.5

43.0

40.6

40.6

80

27.1

34.7

39.0

39.1

26.9

34.4

38.7

38.9

26.6

34.1

38.4

38.7

28.6

36.7

39.5

39.7

30.6

39.2

40.6

40.6

77

23.7

31.3

35.6

35.7

22.8

30.4

34.7

34.9

22.0

29.5

33.7

34.1

23.3

31.4

34.2

34.4

24.6

33.2

34.6

34.7

74

20.2

27.9

32.2

32.3

18.8

26.3

30.6

30.8

17.3

24.8

29.0

29.4

18.0

26.0

28.9

29.1

18.6

27.3

28.7

28.7

71

-

24.5

28.8

28.8

-

22.3

26.6

26.8

-

20.1

24.4

24.7

-

20.7

23.5

23.7

-

21.3

22.7

22.8

68

-

21.0

25.3

25.4

-

18.3

22.5

22.7

-

15.5

19.7

20.1

-

15.4

18.2

18.4

-

15.3

16.7

16.8

125 °F

NET CAP.

MBH

46.4

39.6

38.2

38.3

45.1

38.4

37.1

37.2

43.7

37.1

36.0

36.1

44.5

37.7

36.5

36.7

45.2

38.3

37.1

37.3

TOTAL POWER

INPUT kW

5.70

5.70

5.70

5.60

5.70

5.70

5.70

5.70

5.80

5.80

5.80

5.70

5.90

5.90

5.90

5.90

6.00

6.10

6.10

6.00

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

36.1

43.7

38.2

38.3

35.6

41.0

37.1

37.2

35.1

38.3

36.0

36.1

38.1

38.3

36.5

36.7

41.1

38.3

37.1

37.3

83

32.6

40.6

39.2

39.2

31.5

38.9

37.6

37.7

30.4

37.3

36.0

36.1

32.8

38.5

36.5

36.7

35.2

39.7

37.1

37.3

80

29.2

37.2

40.9

40.9

27.5

34.9

38.2

38.4

25.7

32.6

35.5

36.0

27.5

34.8

36.3

36.6

29.2

37.0

37.1

37.3

77

25.8

33.7

37.5

37.5

23.4

30.8

34.2

34.4

21.1

26.0

30.9

31.3

22.2

29.0

31.0

31.3

23.3

31.1

31.2

31.3

74

22.4

30.3

34.0

34.1

19.4

26.8

30.1

30.4

16.4

23.3

26.2

26.7

16.8

24.2

25.7

26.0

17.3

25.1

25.2

25.4

71

-

26.9

30.6

30.6

-

22.8

26.1

26.3

-

18.6

21.5

22.0

-

18.9

20.4

20.7

-

19.1

19.2

19.4

68

-

23.5

27.2

27.2

-

18.7

22.0

22.3

-

14.0

16.9

17.3

-

13.6

15.1

15.4

-

13.2

13.3

13.4

1.

These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY