All sensible capacity – York DNH018 User Manual
Page 11
036-21233-002-A-0903
Unitary Products Group
11
TABLE 6: DNH036 COOLING CAPACITIES - 3 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
900 CFM
1,050 CFM
1,200 CFM
1,300 CFM
1,400 CFM
WB °F
WB °F
WB °F
WB °F
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85 °F
NET CAP.
MBH
35.9
33.6
31.7
31.6
38.4
35.9
33.9
33.8
40.9
38.3
36.1
36.0
41.5
38.9
36.6
36.6
42.1
39.5
37.2
37.2
TOTAL POWER
INPUT kW
3.14
3.09
3.10
3.17
3.16
3.11
3.12
3.18
3.18
3.13
3.14
3.20
3.12
3.07
3.08
3.14
3.07
3.02
3.03
3.09
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
19.7
25.4
30.8
30.9
23.6
29.9
33.4
33.5
27.5
34.4
36.1
36.0
26.6
33.9
36.6
36.6
25.8
33.4
37.2
37.2
83
18.7
24.5
29.8
30.0
21.6
28.0
33.0
33.0
24.5
31.5
36.1
36.0
24.6
31.9
36.6
36.6
24.7
32.3
37.2
37.2
80
17.8
23.5
28.9
29.1
19.7
26.0
32.0
32.2
21.6
28.5
35.0
35.2
22.6
29.8
36.1
36.2
23.6
31.2
37.2
37.2
77
16.9
22.6
28.0
28.2
17.7
24.1
30.0
30.2
18.6
25.5
32.1
32.3
20.6
27.8
34.1
34.2
22.5
30.1
36.1
36.1
74
15.9
21.7
27.1
27.2
15.8
22.1
28.1
28.3
15.6
22.6
29.1
29.3
18.5
25.8
32.1
32.1
21.4
29.0
35.0
35.0
71
-
20.7
26.1
26.3
-
20.2
26.1
26.3
-
19.6
26.1
26.3
-
23.8
30.0
30.1
-
27.9
34.0
33.9
68
-
19.8
25.2
25.4
-
18.2
24.2
24.4
-
16.7
23.2
23.4
-
21.7
28.0
28.1
-
26.8
32.9
32.8
95 °F
NET CAP.
MBH
35.7
32.4
30.5
30.7
38.1
34.5
32.5
32.8
40.5
36.7
34.5
34.8
41.3
37.5
35.3
35.5
42.2
38.2
36.0
36.3
TOTAL POWER
INPUT kW
3.19
3.15
3.14
3.22
3.34
3.30
3.29
3.37
3.49
3.45
3.44
3.53
3.42
3.38
3.37
3.45
3.35
3.31
3.30
3.38
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
23.1
28.6
30.5
30.7
25.5
31.7
32.5
32.8
28.0
34.8
34.5
34.8
26.8
33.8
35.3
35.5
25.6
32.9
36.0
36.3
83
20.4
25.9
30.5
30.6
22.6
28.7
32.5
32.7
24.8
31.5
34.5
34.8
24.6
31.7
35.3
35.5
24.5
31.8
36.0
36.3
80
17.7
23.3
28.1
27.9
19.6
25.8
31.1
30.9
21.6
28.3
34.2
33.9
22.5
29.5
35.1
35.1
23.4
30.7
36.0
36.3
77
15.0
20.6
25.4
25.2
16.7
22.8
28.2
28.0
18.4
25.1
31.0
30.7
20.3
27.4
33.0
33.0
22.3
29.7
34.9
35.2
74
12.3
17.9
22.7
22.5
13.7
19.9
25.2
25.0
15.1
21.9
27.8
27.5
18.2
25.2
30.8
30.8
21.2
28.6
33.8
34.1
71
-
15.2
20.0
19.8
-
16.9
22.3
22.0
-
18.7
24.5
24.3
-
23.1
28.6
28.7
-
27.5
32.7
33.0
68
-
12.5
17.3
17.1
-
14.0
19.3
19.1
-
15.5
21.3
21.1
-
20.9
26.5
26.5
-
26.4
31.7
31.9
105 °F
NET CAP.
MBH
33.7
30.4
28.5
28.7
36.2
32.7
30.6
30.8
38.7
34.9
32.6
32.9
39.3
35.4
33.2
33.4
39.9
36.0
33.7
33.9
TOTAL POWER
INPUT kW
3.66
3.63
3.61
3.70
3.76
3.72
3.70
3.79
3.85
3.81
3.79
3.88
3.77
3.74
3.72
3.81
3.70
3.66
3.64
3.73
S
e
n
s
ib
le
C
apaci
ty
MB
H
1
E
n
te
ring
Dry
Bu
lb
°
F
86
20.6
25.9
28.3
28.3
23.0
28.9
30.5
30.6
25.3
31.8
32.6
32.9
25.2
32.0
33.2
33.4
25.1
32.2
33.7
33.9
83
18.9
24.2
27.9
27.8
21.0
26.9
30.3
30.4
23.2
29.7
32.6
32.9
23.6
30.4
33.2
33.4
24.0
31.1
33.7
33.9
80
17.1
22.4
26.3
26.0
19.1
25.0
29.4
29.1
21.1
27.6
32.4
32.1
22.0
28.8
33.1
33.0
23.0
30.1
33.7
33.9
77
15.4
20.7
24.6
24.3
17.2
23.1
27.5
27.1
19.0
25.5
30.4
30.0
20.5
27.3
31.5
31.4
21.9
29.0
32.6
32.9
74
13.6
18.9
22.8
22.5
15.3
21.2
25.6
25.2
16.9
23.4
28.3
27.9
18.9
25.7
29.9
29.9
20.9
28.0
31.6
31.8
71
-
17.2
21.1
20.8
-
19.3
23.6
23.3
-
21.3
26.2
25.8
-
24.1
28.3
28.3
-
26.9
30.5
30.8
68
-
15.4
19.3
19.0
-
17.3
21.7
21.4
-
19.3
24.1
23.7
-
22.5
26.8
26.7
-
25.8
29.4
29.7
115 °F
NET CAP.
MBH
31.8
28.5
26.5
26.8
34.3
30.8
28.6
28.9
36.8
33.1
30.7
31.0
37.2
33.4
31.0
31.3
37.5
33.7
31.3
31.6
TOTAL POWER
INPUT kW
4.14
4.11
4.08
4.17
4.17
4.14
4.11
4.21
4.20
4.17
4.14
4.24
4.12
4.09
4.06
4.16
4.04
4.02
3.98
4.08
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
18.2
23.2
26.2
25.8
20.4
26.0
28.5
28.4
22.6
28.9
30.7
31.0
23.6
30.1
31.0
31.3
24.6
31.4
31.3
31.6
83
17.4
22.4
25.4
25.0
19.5
25.1
28.1
28.0
21.6
27.9
30.7
31.0
22.6
29.1
31.0
31.3
23.5
30.4
31.3
31.6
80
16.5
21.6
24.6
24.2
18.6
24.3
27.6
27.2
20.6
26.9
30.7
30.2
21.6
28.1
31.0
30.9
22.5
29.4
31.3
31.6
77
15.7
20.8
23.8
23.4
17.7
23.4
26.8
26.3
19.7
26.0
29.7
29.2
20.6
27.2
30.0
29.9
21.5
28.4
30.3
30.6
74
14.9
20.0
23.0
22.6
16.8
22.5
25.9
25.4
18.7
25.0
28.8
28.3
19.6
26.2
29.0
28.9
20.5
27.3
29.3
29.6
71
-
19.2
22.2
21.8
-
21.6
25.0
24.5
-
24.0
27.8
27.3
-
25.2
28.0
27.9
-
26.3
28.3
28.6
68
-
18.3
21.4
21.0
-
20.7
24.1
23.7
-
23.1
26.8
26.3
-
24.2
27.0
26.9
-
25.3
27.2
27.5
125 °F
NET CAP.
MBH
29.8
26.6
24.5
24.8
32.4
28.9
26.7
27.0
35.0
31.3
28.8
29.1
35.1
31.3
28.9
29.2
35.2
31.4
29.0
29.3
TOTAL POWER
INPUT kW
4.61
4.59
4.55
4.65
4.58
4.56
4.52
4.62
4.55
4.54
4.49
4.59
4.47
4.45
4.41
4.51
4.38
4.37
4.32
4.42
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
15.7
20.5
24.1
23.4
17.8
23.2
26.5
26.3
19.9
25.9
28.8
29.1
21.9
28.3
28.9
29.2
24.0
30.7
29.0
29.3
83
15.8
20.6
22.9
22.3
17.9
23.3
25.9
25.7
20.0
26.1
28.8
29.1
21.5
27.9
28.9
29.2
23.0
29.7
29.0
29.3
80
16.0
20.8
22.9
22.4
18.1
23.5
25.9
25.4
20.2
26.2
28.9
28.3
21.1
27.5
28.9
28.8
22.1
28.7
29.0
29.3
77
16.1
20.9
23.0
22.5
18.2
23.6
26.0
25.5
20.3
26.4
29.1
28.5
20.7
27.0
28.5
28.4
21.1
27.7
28.0
28.3
74
16.2
21.0
23.1
22.6
18.4
23.8
26.2
25.6
20.5
26.5
29.2
28.6
20.3
26.6
28.1
28.0
20.1
26.7
27.0
27.3
71
-
21.1
23.3
22.8
-
23.9
26.3
25.8
-
26.7
29.4
28.8
-
26.2
27.7
27.6
-
25.7
26.0
26.3
68
-
21.3
23.4
22.9
-
24.1
26.5
25.9
-
26.9
29.6
29.0
-
25.8
27.3
27.1
-
24.7
25.0
25.3
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY