All sensible capacity – York DNH018 User Manual

Page 11

background image

036-21233-002-A-0903

Unitary Products Group

11

TABLE 6: DNH036 COOLING CAPACITIES - 3 TON

TEMPERATURE

OF AIR ON

CONDENSER COIL

AIR ON EVAPORATOR COIL

900 CFM

1,050 CFM

1,200 CFM

1,300 CFM

1,400 CFM

WB °F

WB °F

WB °F

WB °F

WB °F

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

85 °F

NET CAP.

MBH

35.9

33.6

31.7

31.6

38.4

35.9

33.9

33.8

40.9

38.3

36.1

36.0

41.5

38.9

36.6

36.6

42.1

39.5

37.2

37.2

TOTAL POWER

INPUT kW

3.14

3.09

3.10

3.17

3.16

3.11

3.12

3.18

3.18

3.13

3.14

3.20

3.12

3.07

3.08

3.14

3.07

3.02

3.03

3.09

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

19.7

25.4

30.8

30.9

23.6

29.9

33.4

33.5

27.5

34.4

36.1

36.0

26.6

33.9

36.6

36.6

25.8

33.4

37.2

37.2

83

18.7

24.5

29.8

30.0

21.6

28.0

33.0

33.0

24.5

31.5

36.1

36.0

24.6

31.9

36.6

36.6

24.7

32.3

37.2

37.2

80

17.8

23.5

28.9

29.1

19.7

26.0

32.0

32.2

21.6

28.5

35.0

35.2

22.6

29.8

36.1

36.2

23.6

31.2

37.2

37.2

77

16.9

22.6

28.0

28.2

17.7

24.1

30.0

30.2

18.6

25.5

32.1

32.3

20.6

27.8

34.1

34.2

22.5

30.1

36.1

36.1

74

15.9

21.7

27.1

27.2

15.8

22.1

28.1

28.3

15.6

22.6

29.1

29.3

18.5

25.8

32.1

32.1

21.4

29.0

35.0

35.0

71

-

20.7

26.1

26.3

-

20.2

26.1

26.3

-

19.6

26.1

26.3

-

23.8

30.0

30.1

-

27.9

34.0

33.9

68

-

19.8

25.2

25.4

-

18.2

24.2

24.4

-

16.7

23.2

23.4

-

21.7

28.0

28.1

-

26.8

32.9

32.8

95 °F

NET CAP.

MBH

35.7

32.4

30.5

30.7

38.1

34.5

32.5

32.8

40.5

36.7

34.5

34.8

41.3

37.5

35.3

35.5

42.2

38.2

36.0

36.3

TOTAL POWER

INPUT kW

3.19

3.15

3.14

3.22

3.34

3.30

3.29

3.37

3.49

3.45

3.44

3.53

3.42

3.38

3.37

3.45

3.35

3.31

3.30

3.38

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

23.1

28.6

30.5

30.7

25.5

31.7

32.5

32.8

28.0

34.8

34.5

34.8

26.8

33.8

35.3

35.5

25.6

32.9

36.0

36.3

83

20.4

25.9

30.5

30.6

22.6

28.7

32.5

32.7

24.8

31.5

34.5

34.8

24.6

31.7

35.3

35.5

24.5

31.8

36.0

36.3

80

17.7

23.3

28.1

27.9

19.6

25.8

31.1

30.9

21.6

28.3

34.2

33.9

22.5

29.5

35.1

35.1

23.4

30.7

36.0

36.3

77

15.0

20.6

25.4

25.2

16.7

22.8

28.2

28.0

18.4

25.1

31.0

30.7

20.3

27.4

33.0

33.0

22.3

29.7

34.9

35.2

74

12.3

17.9

22.7

22.5

13.7

19.9

25.2

25.0

15.1

21.9

27.8

27.5

18.2

25.2

30.8

30.8

21.2

28.6

33.8

34.1

71

-

15.2

20.0

19.8

-

16.9

22.3

22.0

-

18.7

24.5

24.3

-

23.1

28.6

28.7

-

27.5

32.7

33.0

68

-

12.5

17.3

17.1

-

14.0

19.3

19.1

-

15.5

21.3

21.1

-

20.9

26.5

26.5

-

26.4

31.7

31.9

105 °F

NET CAP.

MBH

33.7

30.4

28.5

28.7

36.2

32.7

30.6

30.8

38.7

34.9

32.6

32.9

39.3

35.4

33.2

33.4

39.9

36.0

33.7

33.9

TOTAL POWER

INPUT kW

3.66

3.63

3.61

3.70

3.76

3.72

3.70

3.79

3.85

3.81

3.79

3.88

3.77

3.74

3.72

3.81

3.70

3.66

3.64

3.73

S

e

n

s

ib

le

C

apaci

ty

MB

H

1

E

n

te

ring

Dry

Bu

lb

°

F

86

20.6

25.9

28.3

28.3

23.0

28.9

30.5

30.6

25.3

31.8

32.6

32.9

25.2

32.0

33.2

33.4

25.1

32.2

33.7

33.9

83

18.9

24.2

27.9

27.8

21.0

26.9

30.3

30.4

23.2

29.7

32.6

32.9

23.6

30.4

33.2

33.4

24.0

31.1

33.7

33.9

80

17.1

22.4

26.3

26.0

19.1

25.0

29.4

29.1

21.1

27.6

32.4

32.1

22.0

28.8

33.1

33.0

23.0

30.1

33.7

33.9

77

15.4

20.7

24.6

24.3

17.2

23.1

27.5

27.1

19.0

25.5

30.4

30.0

20.5

27.3

31.5

31.4

21.9

29.0

32.6

32.9

74

13.6

18.9

22.8

22.5

15.3

21.2

25.6

25.2

16.9

23.4

28.3

27.9

18.9

25.7

29.9

29.9

20.9

28.0

31.6

31.8

71

-

17.2

21.1

20.8

-

19.3

23.6

23.3

-

21.3

26.2

25.8

-

24.1

28.3

28.3

-

26.9

30.5

30.8

68

-

15.4

19.3

19.0

-

17.3

21.7

21.4

-

19.3

24.1

23.7

-

22.5

26.8

26.7

-

25.8

29.4

29.7

115 °F

NET CAP.

MBH

31.8

28.5

26.5

26.8

34.3

30.8

28.6

28.9

36.8

33.1

30.7

31.0

37.2

33.4

31.0

31.3

37.5

33.7

31.3

31.6

TOTAL POWER

INPUT kW

4.14

4.11

4.08

4.17

4.17

4.14

4.11

4.21

4.20

4.17

4.14

4.24

4.12

4.09

4.06

4.16

4.04

4.02

3.98

4.08

Se

n

s

ib

le

Ca

p

a

city

MB

H

1

E

n

ter

ing D

ry

Bu

lb

°

F

86

18.2

23.2

26.2

25.8

20.4

26.0

28.5

28.4

22.6

28.9

30.7

31.0

23.6

30.1

31.0

31.3

24.6

31.4

31.3

31.6

83

17.4

22.4

25.4

25.0

19.5

25.1

28.1

28.0

21.6

27.9

30.7

31.0

22.6

29.1

31.0

31.3

23.5

30.4

31.3

31.6

80

16.5

21.6

24.6

24.2

18.6

24.3

27.6

27.2

20.6

26.9

30.7

30.2

21.6

28.1

31.0

30.9

22.5

29.4

31.3

31.6

77

15.7

20.8

23.8

23.4

17.7

23.4

26.8

26.3

19.7

26.0

29.7

29.2

20.6

27.2

30.0

29.9

21.5

28.4

30.3

30.6

74

14.9

20.0

23.0

22.6

16.8

22.5

25.9

25.4

18.7

25.0

28.8

28.3

19.6

26.2

29.0

28.9

20.5

27.3

29.3

29.6

71

-

19.2

22.2

21.8

-

21.6

25.0

24.5

-

24.0

27.8

27.3

-

25.2

28.0

27.9

-

26.3

28.3

28.6

68

-

18.3

21.4

21.0

-

20.7

24.1

23.7

-

23.1

26.8

26.3

-

24.2

27.0

26.9

-

25.3

27.2

27.5

125 °F

NET CAP.

MBH

29.8

26.6

24.5

24.8

32.4

28.9

26.7

27.0

35.0

31.3

28.8

29.1

35.1

31.3

28.9

29.2

35.2

31.4

29.0

29.3

TOTAL POWER

INPUT kW

4.61

4.59

4.55

4.65

4.58

4.56

4.52

4.62

4.55

4.54

4.49

4.59

4.47

4.45

4.41

4.51

4.38

4.37

4.32

4.42

S

e

nsi

b

le

C

apaci

ty

MB

H

1

En

te

ri

n

g

Dr

y

Bu

lb

°

F

86

15.7

20.5

24.1

23.4

17.8

23.2

26.5

26.3

19.9

25.9

28.8

29.1

21.9

28.3

28.9

29.2

24.0

30.7

29.0

29.3

83

15.8

20.6

22.9

22.3

17.9

23.3

25.9

25.7

20.0

26.1

28.8

29.1

21.5

27.9

28.9

29.2

23.0

29.7

29.0

29.3

80

16.0

20.8

22.9

22.4

18.1

23.5

25.9

25.4

20.2

26.2

28.9

28.3

21.1

27.5

28.9

28.8

22.1

28.7

29.0

29.3

77

16.1

20.9

23.0

22.5

18.2

23.6

26.0

25.5

20.3

26.4

29.1

28.5

20.7

27.0

28.5

28.4

21.1

27.7

28.0

28.3

74

16.2

21.0

23.1

22.6

18.4

23.8

26.2

25.6

20.5

26.5

29.2

28.6

20.3

26.6

28.1

28.0

20.1

26.7

27.0

27.3

71

-

21.1

23.3

22.8

-

23.9

26.3

25.8

-

26.7

29.4

28.8

-

26.2

27.7

27.6

-

25.7

26.0

26.3

68

-

21.3

23.4

22.9

-

24.1

26.5

25.9

-

26.9

29.6

29.0

-

25.8

27.3

27.1

-

24.7

25.0

25.3

1.

These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY