TABLE 13: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230, 460 & 575 VOLTS

1

MODEL #

DNH

(Cooling/

Heating)

MTR

SPD

EXTERNAL STATIC PRESSURE - IWG

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

1.10

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

CF

M

W

A

TTS

018

HI

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

620

409

511

392

-

-

MED

-

-

-

-

-

-

-

-

-

-

-

-

635

252

529

231

423

423

-

-

-

-

LOW

-

-

-

-

-

-

649

230

586

217

523

204

460

191

-

-

-

-

-

-

-

-

024

HI

-

-

-

-

-

-

-

-

-

-

-

-

836

442

728

425

620

409

-

-

-

-

MED

-

-

-

-

899

318

850

304

778

287

707

269

635

252

-

-

-

-

-

-

-

-

LOW

898

335

815

300

732

265

649

230

586

217

-

-

-

-

-

-

-

-

-

-

-

-

030

HI

-

-

-

-

-

-

1080

504

999

483

917

463

836

442

728

425

-

-

-

-

-

-

MED

999

345

949

331

899

318

850

304

778

287

707

269

-

-

-

-

-

-

-

-

-

-

LOW

898

335

815

300

732

265

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

036

HI

-

-

-

-

-

-

-

-

-

-

1436

735

1345

705

1189 667 1032

628

-

-

-

-

MED

-

-

-

-

1490

652

1422

625

1339

602

1257

578

1174

555

1049 526

953

497

-

-

-

-

LOW

1387

582

1330

569

1274

555

1217

542

1148

520

1079

497

1010

475

-

-

-

-

-

-

-

-

042

HI

-

-

-

-

1695

821

1618

796

1527

766

1436

735

1345

705

1189 667

-

-

-

-

-

-

MED

1625

707

1557

680

1490

652

1422

625

1339

602

1257

578

1174

555

-

-

-

-

-

-

-

-

LOW

1387

582

1330

569

1274

555

1217

542

1148

520

1079

497

-

-

-

-

-

-

-

-

-

-

048

HI

1768

844

1720

824

1672

804

1613

779

1554

754

1484

727

1414

700

1290 663

-

-

-

-

-

-

MED

1641

754

1594

730

1547

707

1495

683

1442

660

1379

633

1316

606

-

-

-

-

-

-

-

-

LOW

1550

663

1513

645

1477

626

1428

608

1378

590

1324

564

1270

539

-

-

-

-

-

-

-

-

060

(only

575 volts)

HI

2326 1280 2283 1230 2200 1200 2123 1163 2045 1125 1953 1085 1860 1045 1698 990 1535

935

-

-

-

-

MED

2159 1125 2098 1090 2036 1055 1967 1020 1897

985

1814

945

1731

905

1578 582

-

-

-

-

-

-

LOW

1937

990

1892

983

1846

935

1785

908

1723

880

1655

843

1587

805

-

-

-

-

-

-

-

-

060

(3 tube)

(only 230 &

460 volts)

HEAT 1500

245

1500

297

1500

348

1500

400

1500

470

1500

540

1500

610

1500 680 1500

750

1500 820 1500 890

060

(4 & 5 tube)

(only 230 &

460 volts)

HEAT 1700

390

1700

443

1700

497

1700

550

1700

620

1700

690

1700

760

1700 830 1700

900

1700 970

-

-

060

(factory
setting)

(only 230 &

460 volts)

COOL 1800

460

1800

515

1800

570

1800

625

1800

690

1800

755

1800

820

1800 962 1800 1105

-

-

-

-

060

(field

setting)

(only 230 &

460 volts)

COOL 2000

640

2000

700

2000

760

2000

820

2000

928

2000 1035

-

-

-

-

-

-

-

-

-

-

1.

Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to
Tables 14 and 15.

TABLE 14: ADDITIONAL STATIC PRESSURE RESISTANCE 1-1/2 - 3 TON (DNH018 - 036)

1

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

.05

.06

.07

.08

.09

.09

ECONOMIZER

2

.00

.00

.00

.01

.01

.01

.01

.02

.03

.04

.05

.06

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

.13

.16

.17

.18

.19

.20

1.

Deduct these resistance values from the available external static pressure shown in Tables 10, 11, 12, and 13.

2.

The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.