Table 16: electrical data – York DNH018 User Manual
Page 20
036-21233-002-A-0903
20
Unitary Products Group
TABLE 16: ELECTRICAL DATA
MODEL
DNH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
018
208/230-1-60
187
253
7.1
48
1.1
2.6
12.5
15
15
.96
40
024
208/230-1-60
187
253
9.3
57
1.1
2.6
15.3
20
20
.96
40
030
208/230-1-60
187
253
13.6
67
1.1
2.6
20.7
30
30
.96
40
030
208/230-3-60
187
253
8.6
55
1.1
2.6
14.5
20
20
.96
75
030
460-3-60
414
504
4.3
27
0.6
1.4
7.4
15
15
.96
75
036
208/230-1-60
187
253
17.2
88
1.1
3.5
26.1
35
35
.96
40
036
208/230-3-60
187
253
11.4
77
1.1
3.5
18.9
25
25
.96
75
036
460-3-60
414
504
5.7
39
0.6
1.8
9.5
15
15
.96
75
036
575-3-60
518
630
4.7
31
0.4
1.5
7.8
15
15
.96
75
042
208/230-1-60
187
253
20.0
104
1.3
3.5
29.8
40
40
.96
40
042
208/230-3-60
187
253
13.9
88
1.3
3.5
22.2
30
30
.96
75
042
460-3-60
414
504
6.4
44
0.7
1.8
10.5
15
15
.96
75
042
575-3-60
518
630
5.4
34
0.5
1.5
8.8
15
15
.96
75
048
208/230-1-60
187
253
23.4
126
1.9
4.2
35.4
45
45
.96
40
048
208/230-3-60
187
253
13.0
93
1.9
4.2
22.4
30
30
.96
75
048
460-3-60
414
504
6.4
46.5
1.0
2.1
11.1
15
15
.96
75
048
575-3-60
518
630
5.1
37.2
0.8
1.7
8.9
15
15
.96
75
060
208/230-1-60
187
253
32.1
148
1.9
9.4
51.4
70
70
.96
40
060
208/230-3-60
187
253
19.3
123
1.9
9.4
35.4
45
45
.96
75
060
460-3-60
414
504
10.0
62
1.0
9.4
18.2
25
25
.96
75
060
575-3-60
518
630
7.9
50
0.8
2.8
13.5
20
20
.96
75
1.
Utilization range “A” in accordance with ARI Standard 110.
2.
Dual element, time delay type.