All sensible capacity – York DNH018 User Manual
Page 12
036-21233-002-A-0903
12
Unitary Products Group
TABLE 7: DNH042 COOLING CAPACITIES - 3-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,050 CFM
1,225 CFM
1,400 CFM
1,575 CFM
1,750 CFM
WB °F
WB °F
WB °F
WB °F
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85 °F
NET CAP.
MBH
38.6
38.4
34.0
33.3
42.1
41.8
37.0
36.3
45.5
45.3
40.1
39.2
45.3
45.0
39.9
39.1
45.1
44.8
39.7
38.9
TOTAL POWER
INPUT kW
4.05
3.83
3.95
3.91
4.01
3.79
3.92
3.87
3.98
3.76
3.88
3.84
4.12
3.90
4.02
3.98
4.27
4.03
4.16
4.12
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
25.5
32.6
34.0
33.3
28.9
36.8
37.0
36.3
32.2
41.0
40.1
39.2
34.4
42.9
39.9
39.1
36.6
44.8
39.7
38.9
83
22.5
29.6
34.0
33.3
25.4
33.3
37.0
36.3
28.2
36.9
40.1
39.2
29.8
38.9
39.9
39.1
31.4
40.9
39.7
38.9
80
19.6
26.6
31.9
31.9
21.8
29.7
35.6
35.6
24.1
32.8
39.3
39.2
25.1
34.3
39.5
39.1
26.2
35.7
39.7
38.9
77
16.6
23.6
28.9
28.9
18.3
26.2
32.1
32.0
20.0
28.7
35.2
35.2
20.5
29.6
34.8
34.4
21.0
30.5
34.5
33.6
74
13.6
20.7
25.9
25.9
14.7
22.7
28.5
28.5
15.9
24.7
31.1
31.1
15.8
25.0
30.2
29.8
15.8
25.3
29.2
28.4
71
-
17.7
22.9
22.9
-
19.1
25.0
24.9
-
20.6
27.1
27.0
-
20.3
25.5
25.1
-
20.1
24.0
23.2
68
-
14.7
19.9
19.9
-
15.6
21.5
21.4
-
16.5
23.0
22.9
-
15.7
20.9
20.5
-
14.9
18.8
18.0
105 °F
NET CAP.
MBH
36.8
36.2
32.1
31.6
40.2
39.5
35.1
34.5
43.6
42.9
38.1
37.5
43.4
42.7
37.9
37.3
43.3
42.6
37.8
37.2
TOTAL POWER
INPUT kW
4.45
4.20
4.29
4.28
4.41
4.17
4.25
4.24
4.37
4.13
4.21
4.20
4.51
4.26
4.34
4.33
4.65
4.39
4.48
4.46
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
25.5
32.1
32.1
31.6
28.9
36.2
35.1
34.5
32.2
40.4
38.1
37.5
34.6
41.5
37.9
37.3
36.9
42.6
37.8
37.2
83
22.5
29.1
32.1
31.6
25.3
32.7
35.1
34.5
28.1
36.3
38.1
37.5
29.9
38.5
37.9
37.3
31.7
40.7
37.8
37.2
80
19.5
26.1
30.6
30.4
21.8
29.2
34.2
33.9
24.1
32.2
37.8
37.5
25.3
33.8
37.8
37.3
26.5
35.4
37.8
37.2
77
16.5
23.1
27.7
27.4
18.3
25.6
30.7
30.4
20.0
28.1
33.7
33.4
20.6
29.2
33.1
32.7
21.3
30.2
32.6
32.0
74
13.5
20.1
24.7
24.4
14.7
22.1
27.1
26.8
15.9
24.0
29.6
29.3
16.0
24.5
28.5
28.0
16.1
25.0
27.4
26.8
71
-
17.1
21.7
21.4
-
18.5
23.6
23.3
-
19.9
25.5
25.2
-
19.9
23.8
23.4
-
19.8
22.2
21.6
68
-
14.1
18.7
18.4
-
15.0
20.1
19.8
-
15.9
21.5
21.1
-
15.2
19.2
18.7
-
14.6
16.9
16.3
115 °F
NET CAP.
MBH
35.4
33.7
29.9
29.5
38.7
36.8
32.7
32.2
42.1
40.0
35.5
35.0
41.8
39.7
35.2
34.8
41.4
39.4
35.0
34.5
TOTAL POWER
INPUT kW
4.80
4.64
4.73
4.72
4.78
4.62
4.71
4.70
4.75
4.59
4.68
4.67
4.88
4.71
4.80
4.80
5.00
4.83
4.93
4.92
S
e
n
s
ib
le
C
apaci
ty
MB
H
1
E
n
te
ring
Dry
Bu
lb
°
F
86
24.8
31.0
29.9
29.5
28.2
34.9
32.7
32.2
31.6
38.7
35.5
35.0
34.0
39.1
36.2
34.8
36.3
39.4
35.0
34.5
83
21.8
28.0
29.9
29.5
24.7
31.6
32.7
32.2
27.5
35.3
35.5
35.0
29.3
36.8
35.2
34.8
31.1
38.4
35.0
34.5
80
18.8
25.0
28.4
28.1
21.1
28.1
31.9
31.6
23.5
31.2
35.4
35.0
24.7
32.8
35.2
34.8
25.9
34.4
35.0
34.5
77
15.8
22.0
25.4
25.1
17.6
24.6
28.3
28.0
19.4
27.1
31.3
30.9
20.0
28.2
30.5
30.1
20.7
29.2
29.7
29.3
74
12.8
19.0
22.4
22.1
14.1
21.0
24.8
24.5
15.3
23.0
27.2
26.9
15.4
23.5
25.9
25.5
15.5
24.0
24.5
24.1
71
-
16.0
19.4
19.1
-
17.5
21.3
21.0
-
18.9
23.1
22.8
-
18.9
21.2
20.8
-
18.8
19.3
18.8
68
-
13.1
16.4
16.1
-
14.0
17.7
17.4
-
14.9
19.0
18.7
-
14.2
16.6
16.2
-
13.6
14.1
13.6
125 °F
NET CAP.
MBH
34.0
31.1
27.6
27.3
37.3
34.1
30.3
30.0
40.6
37.1
32.9
32.6
40.1
36.6
32.5
32.2
39.6
36.2
32.1
31.8
TOTAL POWER
INPUT kW
5.16
5.08
5.18
5.17
5.14
5.07
5.16
5.16
5.13
5.05
5.15
5.14
5.24
5.17
5.26
5.26
5.36
5.28
5.38
5.37
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
24.1
29.9
27.6
27.3
27.6
33.5
30.3
30.0
31.0
37.1
32.9
32.6
33.4
36.6
32.5
32.2
35.7
36.2
32.1
31.8
83
21.1
26.9
27.6
27.3
24.0
30.6
30.3
30.0
26.9
34.3
32.9
32.6
28.7
35.2
32.5
32.2
30.5
36.2
32.1
31.8
80
18.1
23.9
26.1
25.9
20.5
27.1
29.5
29.2
22.8
30.2
32.9
32.6
24.1
31.8
32.5
32.2
25.3
33.4
32.1
31.8
77
15.1
21.0
23.1
22.9
17.0
23.5
26.0
25.7
18.8
26.1
28.8
28.5
19.4
27.2
27.9
27.5
20.1
28.2
26.9
26.6
74
12.1
18.0
20.1
19.9
13.4
20.0
22.5
22.2
14.7
22.0
24.8
24.4
14.8
22.5
23.2
22.9
14.9
23.0
21.7
21.3
71
-
15.0
17.2
16.9
-
16.4
18.9
18.6
-
17.9
20.7
20.3
-
17.9
18.6
18.2
-
17.8
16.5
16.1
68
-
12.0
14.2
13.9
-
12.9
15.4
15.1
-
13.8
16.6
16.3
-
13.2
13.9
13.6
-
12.6
11.2
10.9
125 °F
NET CAP.
MBH
32.7
28.6
25.4
25.2
35.9
31.4
27.9
27.7
39.1
34.2
30.4
30.2
38.4
33.6
29.8
29.6
37.7
33.0
29.2
29.1
TOTAL POWER
INPUT kW
5.50
5.50
5.60
5.60
5.50
5.50
5.60
5.60
5.50
5.50
5.60
5.60
5.60
5.60
5.70
5.70
5.70
5.70
5.80
5.80
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
23.4
28.9
25.4
25.2
26.9
32.2
27.9
27.7
30.4
35.5
30.4
30.2
32.8
34.2
29.8
29.6
35.2
33.0
29.2
29.1.
83
20.4
25.9
25.4
25.2
23.4
29.6
27.9
27.7
26.3
33.3
30.4
30.2
28.1
33.6
29.8
29.6
29.9
33.9
29.2
29.1
80
17.4
22.9
23.9
23.6
19.8
26.0
27.2
26.9
22.2
29.2
30.5
30.2
23.5
30.8
29.9
29.6
24.7
32.4
29.2
29.1
77
14.4
19.9
20.9
20.6
16.3
22.5
23.7
23.3
18.2
25.1
26.4
26.1
18.8
26.2
25.2
25.0
19.5
27.2
24.0
23.8
74
11.5
16.9
17.9
17.6
12.8
18.9
20.1
19.8
14.1
21.0
22.3
22.0
14.2
21.5
20.6
20.3
14.3
22.0
18.8
18.6
71
-
13.9
14.9
14.6
-
15.4
16.6
16.3
-
16.9
18.3
17.9
-
16.9
15.9
15.7
-
16.8
13.6
13.4
68
-
10.9
11.9
11.6
-
11.9
13.0
12.7
-
12.8
14.2
13.8
-
12.2
11.3
11.0
-
11.6
8.4
8.2
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY