beautypg.com

Request on/off, On/off run state – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 9

background image

02_NVspec_ver202e_pdf.xls 4_Network Variables

4.

4.

4.

4.

Network Variables

1n

Request On/Off

network input SNVT_switch nviOnOff_n;

This input network variable is used for ON or OFF request of the indoor unit or ventilator (in case of
independent operation) .
When the ventilator(LOSSNAY) is registered interlocking with the indoor unit, it will ON (for high speed) and
OFF interlocking with the indoor unit.
This nv is not required to use when operating only from the local side like the local remote controller.

Valid Range

value field : not used

*The value field is set in 0% usually.

state filed : 0 = Indoor or ventilator Off

state filed : 1 = Indoor or ventilator On

: Else = Indoor or ventilator Off

Default Value

The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

2n

On/Off run state

network output SNVT_switch nvoOnOff_n;

This output network variable indicates the present On/Off state of the indoor unit or ventilator.
When the ventilator(LOSSNAY) is registered interlocking with the indoor unit, the state of the ventilator will not
be output, output, but it acts (On/Off) as same as the indoor unit.

Valid Range

value field : not used

*The value field might not be 0,when only the interlocking ventilator(LOSSNAY) unit has been turned on.

state filed : 0 = Indoor or ventilator Off

state filed : 1 = Indoor or ventilator On or TESTRUN
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly as its state changes.
This variable is also transmitted as the state changes by the operation from the local such as the local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.

Update Rate

Update Rate

Update Rate

Update Rate

The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.

Default Service Type

Acknowledged

WLN01-1023(Ver2.02)

- 9 -