Request local prohibit on/off, Local prohibit on/off state – MITSUBISHI ELECTRIC LMAP-02E User Manual
Page 16
02_NVspec_ver202e_pdf.xls 4_Network Variables
19n
Request Local Prohibit On/Off
network input SNVT_switch nviProOnOff_n;
This input network variable is used to prohibit the On/Off operation of the local remote
controller connected to the indoor unit or ventilator (under independent operation without interlocking).
When the ventilator is registered to be interlocked with the indoor unit, the On/Off operation
of the ventilator will also be prohibited.
Valid Range
value field : not used
state field : 0 = Permit On/Off operation of local remote controller
state field : 1 = Prohibit On/Off operation of local remote controller
: Else = Permit On/Off operation of local remote controller
Default Value
The default value permit On/Off operation of local remote controller
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.
NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")
20n
Local Prohibit On/Off state
network output SNVT_switch nvoProOnOff_n;
This output network variable indicates the prohibit/permit state for the On/Off
of the local remote controller connected to the indoor unit or ventilator.
Valid Range
value field : not used = 0 constantly
state field : 0 = Permit On/Off of local remote controller
state field : 1 = Prohibit On/Off of local remote controller
*The value is 0 while LM-AP is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
Update Rate
Update Rate
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")
WLN01-1023(Ver2.02)
- 16 -