beautypg.com

Request local prohibit on/off, Local prohibit on/off state – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 16

background image

02_NVspec_ver202e_pdf.xls 4_Network Variables

19n

Request Local Prohibit On/Off

network input SNVT_switch nviProOnOff_n;

This input network variable is used to prohibit the On/Off operation of the local remote
controller connected to the indoor unit or ventilator (under independent operation without interlocking).
When the ventilator is registered to be interlocked with the indoor unit, the On/Off operation
of the ventilator will also be prohibited.

Valid Range

value field : not used

state field : 0 = Permit On/Off operation of local remote controller

state field : 1 = Prohibit On/Off operation of local remote controller

: Else = Permit On/Off operation of local remote controller

Default Value

The default value permit On/Off operation of local remote controller
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")

20n

Local Prohibit On/Off state

network output SNVT_switch nvoProOnOff_n;

This output network variable indicates the prohibit/permit state for the On/Off
of the local remote controller connected to the indoor unit or ventilator.

Valid Range

value field : not used = 0 constantly

state field : 0 = Permit On/Off of local remote controller

state field : 1 = Prohibit On/Off of local remote controller
*The value is 0 while LM-AP is initialized.

When Transmitted

This variable is transmitted promptly as the state changes.

Update Rate

Update Rate

Update Rate

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")

WLN01-1023(Ver2.02)

- 16 -