Snvt table – MITSUBISHI ELECTRIC LMAP-02E User Manual
Page 8
02_NVspec_ver202e_pdf.xls 3_SNVT Table
3.SNVT Table
3.SNVT Table
3.SNVT Table
3.SNVT Table
Model
Model
Model
Model
nv No.
Name
CITY
Mr.SLIM
SNVT Type
input
output
(note 1)
(note 1)
MULTI
interlocks with
the indoor unit
operation from
L
ON
W
ORKS
Transmitted
when changing
Auto update
Initialize
(note 2)
1n
Request On/Off
nviOnOff_n
X
X
X
SNVT_switch
value
not used
-
-
-
state
X
-
-
-
2n
On/Off run state
nvoOnOff_n
X
X
X
SNVT_switch
value
-
not used
not used
not used
state
-
X
X
X
3n
Request Mode
nviMode_n
X
X
SNVT_hvac_mode
X
-
-
-
4n
Mode state
nvoMode_n
X
X
SNVT_hvac_mode
-
X
X
X
13n
Request LOSNNAY Mode
nviLCMode_n
X(note 3) SNVT_switch
value
X
-
-
-
state
X
-
-
-
14n
LOSSNAY Mode state
nvoLCMode_n
X(note 3)
X(note 3) SNVT_switch
value
-
X
X
X
state
-
not used
not used
not used
5n
SetPoint from network
nviSetPoint_n
X
X
SNVT_temp_p
X
-
-
-
6n
SetPoint state
nvoSetPoint_n
X
X
SNVT_temp_p
-
X
X
X
7n
Request Fanspeed
nviFanSpeed_n
X
X
X
SNVT_switch
value
X
-
-
-
state
not used
-
-
-
8n
FanSpeed state
nvoFanSpeed_n
X
X
X
SNVT_switch
value
-
X
X
X
state
-
not used
not used
not used
10n
Thermo On/Off state
nvoThermo_n
X
X
SNVT_state
-
X
-
-
12n
Temperature state of indoor
nvoSpaceTemp_n
X
X
SNVT_temp_p
-
X
X
-
16n
Alarm state
nvoAlarm_n
X
X
X(note 3)
X(note 3) SNVT_switch
value
-
not used
-
-
state
-
X
-
-
19n
Request Local Prohibit
On/Off
nviProOnOff_n
X
X
SNVT_switch
value
not used
-
-
-
state
X
-
-
-
20n
Local Prohibit On/Off
state
nvoProOnOff_n
X
X
SNVT_switch
value
-
not used
-
-
state
-
X
-
-
21n
Request Local Prohibit
mode
nviProMode_n
X
X
SNVT_switch
value
not used
-
-
-
state
X
-
-
-
22n
Local Prohibit mode state
nvoProMode_n
X
X
SNVT_switch
value
-
not used
-
-
state
-
X
-
-
23n
Request Local Prohibit
SetPoint
nviProSetP_n
X
X
SNVT_switch
value
not used
-
-
-
state
X
-
-
-
24n
Local Prohibit SetPoint
state
nvoProSetP_n
X
X
SNVT_switch
value
-
not used
-
-
state
-
X
-
-
11
Request All Off
nviAllOff
X
X
X
X
SNVT_switch
value
not used
-
-
-
state
X
-
-
-
NOTES:
1.
The value "n" is M-NET address of indoor unit
ex) Request On/Off to the 20th indoor unit.
nvNo :120
Name :nviOnOff_20
2.
The initialization of output can be changed by the setting of the configuration property.
3.
There is a case which cannot be used with the system configuration of the air conditioners units or the model of LOSSNAY.
LOSSNAY
WLN01-1023(Ver2.02)
- 15-