beautypg.com

MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 5

background image

02_NVspec_ver202e_pdf.xls 2_Object Details

2-3.Mr.SLIM

Indoor[1]-[50]

Network Variables

nv1n

nviOnOff_n
SNVT switch

nv2n

nvoOnOff_n
SNVT switch

nv3n

nviMode_n
SNVT hvac mode

nv4n

nvoMode_n
SNVT hvac mode

nv5n

nviSetPoint_n
SNVT temp p

nv6n

nvoSetPoint_n
SNVT temp p

nv7n

nviFanSpeed_n
SNVT switch

nv8n

nvoFanSpeed_n
SNVT switch

nv10n

nvoThermo_n
SNVT state

nv12n

nvoSpaceTemp_n
SNVT temp p

nv16n

nvoAlarm_n
SNVT switch

(note 4,5)

nv19n

nviProOnOff_n
SNVT switch

nv20n

nvoProOnOff_n
SNVT switch

(note 4,5)

(note 4,5)

nv21n

nviProMode_n
SNVT switch

nv22n

nvoProMode_n
SNVT switch

(note 4,5)

(note 4,5)

nv23n

nviProSetP_n
SNVT switch

nv24n

nvoProSetP_n
SNVT switch

(note 4,5)

NOTES:

1. stencil for LonMaker:MrSLIM[1]-[50]
2. "n" of the network variable shows M-NET address of Mr.SLIM.
3. Please turn ON the switch(SW1-6) when Mr.SLIM is operation from L

ON

W

ORKS

.(Factory setting "OFF")

4. There is a case which cannot be used with the system configuration of the air conditioners units.
5. For the use of this function, turn ON the switch(SW1-1) on LM-AP.(Factory setting "OFF")

WLN01-1023(Ver2.02)