beautypg.com

Send heartbeat_1, Send heartbeat_2 – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 20

background image

02_NVspec_ver202e_pdf.xls 5_Configuration

5.Configuration Properties

5.Configuration Properties

5.Configuration Properties

5.Configuration Properties

(1)

Send Heartbeat_1

network input config SNVT_time_sec nciSndHrtBt_1;

This network configuration defines the time between the previous and next updating.
When the set time is elapsed
from the automatic update or change output of the previous nvoOnOff_n (On/Off Run State),
automatic updating will be commenced.
The objective variables are given below.

 ・nvoOnOff_n(On/Off state output)
 ・nvoMode_n(Operating mode output)
 ・nvoLCMode_n(LOSSNAY operation mode output)
 ・nvoSetPoint_n(Temperature setpoint output)
 ・nvoFanSpeed_n(Fan airflow rate output)

Valid Range

The valid range covers from 0.0,600.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 ~ 599.9 seconds results in 600.0seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.

Default Value

6553.5 seconds (without automatic update)

(2)

Send Heartbeat_2

network input config SNVT_time_sec nciSndHrtBt_2;

This network configuration defines the time between the previous and next updating.
When the set time is elapsed from the previous updating, automatic updating will be commenced.
The objective variable is given below.

 ・nvoSpaceTemp_n (Indoor Temperature State)

Valid Range

The valid range covers from 0.0,600.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 ~ 599.9 seconds results in 600.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.

To obtain the output within 10 minutes, set the connecting indoor unit to 30sets or less.
Please turn ON the switch(SW1-3) on LM-AP.(Factory setting "OFF")
The valid range in this case becomes as 0.0,60.0 ~ 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 ~ 59.9 seconds results in 60.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.

Default Value

6553.5seconds (without automatic update)

WLN01-1023(Ver2.02)

- 20 -