02_NVspec_ver202e_pdf.xls AppendixA

Communication timing when power supply of LM-AP is turned on

 

Power Supply

Power Supply

Power Supply

Power Supply

tttt

Initialized Processing

Initialized Processing

Initialized Processing

Initialized Processing

Usually Processing

Usually Processing

Usually Processing

Usually Processing

0

Initialization of LM-AP

(15 minutes or more)

operation(1st Unit)

operation(1st Unit)

L

ON

W

ORKS

No response from NC

・・・・・・・・・・・・

(13 minutes or less)

・・・

1st Unit

2nd Unit

50th Unit

1st Unit

1st Unit

automaic update

automaic update

Initial Output

State change(1st Unit)

State change(1st Unit)

State change(1st Unit)

State change(2nd Unit)

M-NET

1st Unit

1st Unit

1st Unit

2nd Unit

nci

nci

nci

nci

Name

Name

Name

Name

Range

Range

Range

Range

Default

Default

Default

Default

nciSndHrtBt_1

Send Heartbeat_1

0,600~6540,6553.5sec

6553.5sec(without automatic update)

nciSndHrtBt_2

Send Heartbeat_2

0,600~6540,6553.5sec

6553.5sec(without automatic update)

nciMinOutTm

Minimum Send Time

0,0.1~600,6553.5sec

6553.5sec(setting invalid)

nciInitStartTm

Initialize Start Time

0,900~3600,6553.5sec

6553.5sec(setting invalid)

nciInitOutTm_1

Initialize Send Time_1

0,0.1~1.0,6553.5sec

6553.5sec(setting invalid)

nciInitOutTm_2

Initialize Send Time_2

0,0.5~50,6553.5sec

6553.5sec(setting invalid)

nciStartHrtBt

Send Heartbeat Start Time

0,1200~6540,6553.5sec

6553.5sec(judged as 1800 seconds)

nciStartOutTm

Send Start Time

0,1200~6540,6553.5sec

6553.5sec(judged as 1800 seconds)

Centralized

(4)

(1)
(2)
(3)

Controller

LM-AP

Indoor Unit

No.

No.

No.

No.

(5)
(6)
(7)
(8)

(4)nciInitStartTm

(5)nciInitOutTm_1

(8)nciStartOutTm

(7)nciStartHrtBt

(6)nciInitOutTm_2

(1)nciSndHrtBt_1

(3)nciMinOutTm

Data Send

Data Set

(3)nciMinOutTm

(6)nciInitOutTm_2

WLN01-1023(Ver2.02)