02_NVspec_ver202e_pdf.xls 4_Network Variables

10n

Thermo On/Off state

network output SNVT_state nvoThermo_n;

This output network variable indicates the On/Off state of the indoor unit, the thermostat
(compressor command signal) and the auxiliary heater for heating.
This nv is used to calculate the electric charge.

Valid Range

bit[0] : 0 = Indoor Off

bit[0] : 1 = Indoor On

bit[1] : 0 = Indoor thermostat Off (of the indoor unit)

bit[1] : 1 = Indoor thermostat On (of the indoor unit)

bit[2] : 0 = Supplementary heater Off

bit[2] : 1 = Supplementary heater On
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly when the state changes.

Update Rate

Update Rate

Update Rate

Update Rate

The value designated by nciMinOutTm (Minimum Send Time) is valid.

Default Service Type

Acknowledged

12n

Indoor temperature state

network output SNVT_temp_p nvoSpaceTemp_n;

This output network variable indicates the state of the indoor temperature.

Valid Range

Output range : -10~50℃

Temperature unit : 0.1℃
*The value is 0 while LM-AP is initialized.

When Transmitted

This variable is transmitted when the indoor temperature changes by more than 1℃。

(However,it will not be transmitted for changes within 10 minutes.)

*To obtain the output within 10 minutes, please refer to the nciSndHrtBt_2 (Send Heartbeat_2).

Update Rate

Update Rate

Update Rate

Update Rate

The value designated by nciSndHrtBT_2(Send Heartbeat_2) and nciMinOutTm

(Minimum Send Time) is valid.

Default Service Type

Acknowledged

WLN01-1023(Ver2.02)