Request Local Prohibit SetPoint
network input SNVT_switch nviProSetP_n;
This input network variable is used to prohibit the temperature setpoint change of the
local remote controller connected to the indoor unit.
Valid Range
value field : not used
state field : 0 = Permit temperature setpoint change for local remote controller
state field : 1 = Prohibit temperature setpoint change for local remote controller
: Else = Permit temperature setpoint change for local remote controller
Default Value
The default value permit temperature setpoint change for local remote controller.
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.
NOTE: For the use of this function, turn ON the switch(SW1-1) on LM-AP.(Factory setting "OFF")
24n
Local Prohibit SetPoint state
network output SNVT_switch nvoProSetP_n;
This output network variable indicates the prohibit/permit of the temperature setting for
the local remote controller connected to the indoor unit or ventilator.
Valid Range
value field : not used = 0 constantly
state field : 0 = Permit temperature setpoint change for local remote controller
state field : 1 = Prohibit temperature setpoint change for local remote controller
*The value is 0 while LM-AP is initialized.
When Transmitted
This output network variable is transmitted promptly as the state changes.
Update Rate
Update Rate
Update Rate
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")