Alarm state, Update rate – MITSUBISHI ELECTRIC LMAP-02E User Manual
Page 15

02_NVspec_ver202e_pdf.xls 4_Network Variables
16n
Alarm state
network output SNVT_switch nvoAlarm_n;
This output network variable indicates the abnormality of the indoor unit.
If the outdoor unit is in alarm state, the indoor unit also stops urgently.
Therefore all indoor units in a same refrigerant system will transmit alarm state
when the outdoor unit is under alarm state.
However the indoor unit under stopping is excluded.
Valid Range
value field: not used = 0 constantly
state field : 0 = Normal
state field : 1 = Alarm
*The value is 0 while LM-AP is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
Update Rate
Update Rate
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: The release of the indoor unit nvoAlarm_n (Alarm State) results in the "Off"
command of the nviOnOff_n (Request On/Off).
For the nvoAlarm_n (Alarm State) when the indoor unit is under stopping, transmit "Off" .
after transmitting "On"
WLN01-1023(Ver2.02)
- 15 -