Setpoint from network (both cool and heat), Setpoint state (both cool and heat) – MITSUBISHI ELECTRIC LMAP-02E User Manual
Page 12
02_NVspec_ver202e_pdf.xls 4_Network Variables
5n
Setpoint from network (Both cool and heat)
network input SNVT_temp_p nviSetPoint_n;
This input network variable is used to change the temperature setpoint of the indoor unit.
* The set temperature applied is used for cool/dry/heat/auto modes and not for fan mode operation.
This nv is not required to use when setting the temperature only from the local side
such as the local remote controller.
Valid Range
At auto mode : 19 ~ 28 ℃
At heat mode : 17 ~ 28 ℃
At cool mode : 19 ~ 30 ℃
At dry mode : 19 ~ 30 ℃
At fan mode : Not available
Unit of set temperature : 1.0℃
*Be careful that the range of set temperature may differ depending on the model of the
indoor and outdoor units.
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.
6n
Setpoint state (Both cool and heat)
network output SNVT_temp_p nvoSetPoint_n;
This output network variable indicates the present temperature setpoint of the indoor unit.
Valid Range
Output range: 17 ~ 30 ℃
Temperature unit: 1.0 ℃
*The value is 0 while LM-AP is initialized.
When Transmitted
This output network variable is transmitted promptly when the state changes.
This variable is also transmitted as the state changes by the operation from the local such as the local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.
Update Rate
Update Rate
Update Rate
Update Rate
The value defined by nciSndHrtBt_1(SendHearbeat_1) is valid.
Default Service Type
Acknowledged
WLN01-1023(Ver2.02)
- 12 -