Request lossnay mode, Lossnay mode state – MITSUBISHI ELECTRIC LMAP-02E User Manual
Page 11

02_NVspec_ver202e_pdf.xls 4_Network Variables
13n
Request LOSSNAY Mode
network input SNVT_switch nviLCMode_n;
This input network variable is used to change the operation mode of the ventilator
(at independent operation without interlocking) .
This nv is not required to use when setting the operation mode only from the local side such as the
local remote controller. remote controller.
Valid Range
state field : 0 & value field : 0% = LOSSNAY ventilation
state field : 0 & value field : Else = Bypass ventilation
state field : 1 & value field : not care = Damper auto
state field : Else = Damper auto
Default Value
The default value is determined by the state of the ventilator.
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.
14n
LOSSNAY Mode state
network output SNVT_switch nvoLCMode_n;
This output network variable indicates the present operation mode of the ventilator.
Valid Range
value field : 0% =LOSSNAY ventilation
value field : 100% = Bypass ventilation
state field : not used =0 constantly
*The value is 0 while LM-AP is initialized.
When Transmitted
This output network variable is transmitted promptly when the state changes.
It is also transmitted as the state changes by the operation from the local such as the local remote
controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.
Update Rate
Update Rate
Update Rate
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
WLN01-1023(Ver2.02)
- 11 -