02_NVspec_ver202e_pdf.xls 5_Configuration
(7)
Send Heartbeat Start Time
network input config SNVT_time_sec nciStartHrtBt
This configuration property defines the start time of automatic updating at the powering of the LM-AP.
The objective network configurations are given below.
・nciSndHrtBt_1(Send Heartbeat_1)
・nciSndHrtBt_2(Send Heartrbeat_2)
Valid Range
The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 ~ 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds (judged as 1800 seconds)
(8)
Send Start Time
network input config SNVT_time_sec nciStartOutTm
This configuration property defines the start time of the output network variable change at powering of
LM-AP.
The objective network variables are given below.
・nvoOnOff_n(On/Off Run State )
・nvoMode_n(Mode State)
・nvoLCMode_n(LOSSNAY Mode State)
・nvoSetPoint_n(Setpoint State)
・nvoFanSpeed_n(Fan Speed State)
・nvoThermo_n(Thermostat On/Off State )
・nvoSpaceTemp_n(Indoor Temperature State )
・nvoAlarm_n(Alarm State)
・nvoProOnOff_n(Local Prohibit On/Off State)
・nvoProMode_n(Local Prohibit Mode State)
・nvoProSetP_n(Local Prohibit SetPoint State )
Valid Range
The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 ~ 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds (judged as 1800 seconds)
WLN01-1023(Ver2.02)