TDK 2U GENESYS 5KW User Manual
Page 19
83-515-000 Rev. B
11
NOTES:
*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2: Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 190-240Vac (50/60Hz) for 3-Phase 200V models and 380~415Vac (50/60Hz) for 3-
Phase 400V models.
*4: 3-Phase 200V models: at 200Vac input voltage
3-Phase 400V: at 380Vac input voltage. With rated output power.
*5: Not including EMI filter inrush current, less than 0.2mSec.
*6: 3-Phase 200V models: 170~265Vac, constant load.
3-Phase 400V models: 342-460Vac, constant load.
*7: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense.
*8: For 8V~300V models: measured with JEITA RC-9131A (1:1) probe.
For 600V model: measured with 10:1 probe.
*9: From 10% to 90% or 90% to 10% of rated output voltage, with rated, resistive load.
*10: From 90% to 10% of rated output voltage.
*11: For load voltage change, equal to the unit voltage rating, constant input voltage.
*12: For 8V~16V models the ripple is measured at 2V rated output voltage and rated output current.
For other models, the ripple is measured at 10~100% of rated output voltage and rated output
current.
*13: The constant Current programming readback and monitoring accuracy does not include the
warm-up and load regulation thermal drift.
2.12 SUPPLEMENTAL CHARACTERISTICS
The supplemental characteristics give typical but non-warranted performance characteristics. The
supplemental characteristics are useful in assessing applications for the power supply. Several kinds
of supplemental characteristics are listed below.
1. Evaluation Data: Typical performance of the power supply.
2. Reliability Data: Reliability Performance of the power supply.
3. EN61000 Data: Performance of the power supply under EN61000 test conditions.
4. EMI Data: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics data is held in each TDK-Lambda Americas Inc. sales and service
facility. For further details please contact the TDK-Lambda Americas Inc. office nearest you.