Systematic refrigerating cycle diagram – Toshiba RAV-SM800XT-E User Manual
Page 9
– 7 –
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. RAV-SM560XT-E / RAV-SM560AT-E
Pressure
Pipe surface temperature (
°
C)
(MPa)
Discharge
Suction
Indoor heat Outdoor heat
Indoor
exchanger
exchanger
fan
Pd
Ps
(TD)
(TS)
(TC)
(TE)
Indoor
Outdoor
Standard
3.1
0.9
85
13
10
47
74
HIGH
27/19
35/–
Cooling
Overload
3.8
1.0
96
13
12
60
71
HIGH
32/24
43/–
Low load
0.9
0.5
25
7
10
5
28
LOW
18/15.5
–5/–
Standard
2.8
0.6
87
3
46
1
87
HIGH
20/–
7/6
Heating
Overload
3.3
1.1
78
22
55
16
55
LOW
30.–
24/18
Low load
1.7
0.2
110
–20
26
–22
110
HIGH
0
–20/(70%)
Indoor/Outdoor
temp. conditions
(DB/WB) (
°
C)
Compressor
revolutions
per second
(rps)
*
* 4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Indoor unit
Outdoor unit
TCJ
sensor
Air heat exchanger
Strainer
TC sensor
Refrigerant pipe
at liquid side
Outer dia.
∅
B
Refrigerant pipe
at gas side
Outer dia.
∅
A
Packed valve
Outer dia.
∅
B
Packed valve
Outer dia.
∅
A
Max
30m
TS sensor
TD sensor
TO sensor
TE
sensor
Distributor
4-way valve
(VT7101D)
Muffler
∅
19 x L160
Rotary compressor
(DA130A1F-23F)
Heat exchanger
∅
8 multiple thread
ripple 1 row 22 stages
FP1.3 flat fin
PMV
(SKV-18D26)
R410A 0.9 kg
Cooling
Heating
Outer diameter of refrigerant pipe
Gas side
∅
A
Liquid side
∅
B
6.4 mm
12.7 mm