beautypg.com

Toshiba RAV-SM800XT-E User Manual

Page 60

background image

– 58 –

-Cooling and heating model-

Is it possible to start

unit by remote control?

Is it possible to detect

DC 15

60 V between

2

and

3

on terminal block?

Is crossover cable normal?

Is it possible to detect

AC 12 V on secondary side

(CN06) of transformer?

YES

YES

YES

YES

YES

Turn on power supply.

Does OPERATION

lamp blink?

YES

NO

NO

NO

Refer to 9-9 Troubleshooting

for Remote Control .

Connect crossover

cable properly.

NO

NO

NO

Replace outdoor

P.C. board.

Replace outdoor

P.C. board.

Replace outdoor

transformer.

NO

Check TA and TC sensors

or refer to 01

04 in Table 9-4-1.

Is it possible to detect

DC 5 V at Q60 and 12 V at Q50?

YES

Replace MG switch.

NO

Does MG switch operate?

(Next Page)

Is it possible to detect

AC 220

240 V at CN11?

Are TD and TE sensors normal?

(TD=17.9 k

at 50

°

C)

(TE=10 k

at 25

°

C)

YES

Replace sensors.

NO

Refer to item Power

can not be turned on .

All lamps on

indoor unit normal?

YES

NO

Refer to item 9-8-3 How to

check outdoor P.C. board.