Indoor unit, Outdoor unit, Construction views – Toshiba RAV-SM800XT-E User Manual

Page 3: Refrigerating cycle diagram, Wiring diagram, Electrical parts, Refrigerant r410a, Control block diagram, Operation description, Specifications

background image

– 1 –

1. SPECIFICATIONS

1-1. Indoor Unit

Model name

RAV-SM560XT-E

RAV-SM800XT-E

Cooling

Heating

Average

Cooling

Heating

Average

Standard capacity (Note 1)

kW

5.0

5.6

6.7

8.0

(1.5 – 5.6)

(1.5 – 6.3)

(2.2 – 8.0)

(2.2 – 9.0)

Heating low temp. capacity (Note 1) (kW)

4.9

5.8

Energy consumption effect ratio (Cooling)

2.67 [D]

3.29 [C]

2.98

2.46 [E]

3.00 [D]

2.73

Power supply

1 phase 220 – 240V 50Hz

Running current

(A)

8.95 – 8.20

8.13 – 7.46

13.15 – 12.06 12.91 – 11.84

Power consumption

(kW)

1.87

1.7

2.72

2.67

(Low temp.)

(kW)

2.18

2.29

Power factor

(%)

95

95

94

94

Main unit

Pure white

Appearance

Ceiling panel

Model

–––

(Sold separately)

Panel color

–––

Height

(mm)

633

Main unit

Width

(mm)

1093

Outer

Depth

(mm)

208

dimension

Height

(mm)

–––

Width

(mm)

–––

Depth

(mm)

–––

Total weight

Main unit

(kg)

23

Ceiling panel

–––

Heat exchanger

Finned tube

Fan

Multi blade fan

Fan unit

Standard air flow High (Mid./Low)

(m

3

/h)

800 (680/580)

900(750/550)

Motor

(W)

50

Air filter

Washable filter

Controller (Sold separately)

Wireless remote control

Gas side

(mm)

12.7 (1/2”)

15.9 (5/8”)

Dimensions pipe

Liquid side

(mm)

6.4 (1/4”)

9.5 (3/8”)

Drain port

(Nominal dia.)

25 (Polyvinyl chloride tube)

Sound level

High (Mid./Low) (Note 2)

(dB•A)

43

39

36

46

42

37

Electrical
characteristics

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616

based on the reference piping length 7.5 m with 0 meter height.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values

measured in the actual operating environment become larger than the indicated values due to the effects of
external sound.

Note

: Rated conditions

Cooling : Indoor air temperature 27

°

C DB/19

°

C WB, Outdoor air temperature 35

°

C DB

Heating : Indoor air temperature 20

°

C DB, Outdoor air temperature 7

°

C DB/6

°

C WB

Ceiling panel