Toshiba RAV-SM800XT-E User Manual
Page 55
– 53 –
NO
Correct connection of connector.
* For RAV-SM560AT-E, replace the control B.C. board
* Refer to Characteristics-3.
YES
NO
Are characteristics of TE/TS sensor
resistance values normal?
Replace TE and TS sensors.
YES
* (For RAV-SM560AT-E, CN600TE sensor and CN603 TS sensor)
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
Check CDB.
Defect Replace
* Refer to Characteristics-4.
NO
Correct connection of connector.
YES
NO
Are characteristics of TD sensor
resistance value normal?
Replace TD sensors.
YES
* (For RAV-SM560AT-E, CN601 on
control P.C. board)
Is connection of TD sensor connector
of CDB CN600 normal?
Check control P.C. board.
Defect Replace
Is there no abnormal overload?
Are cabling/connector normal?
Was the error just after
power ON determined?
Is IPDU P.C. board come to
closely contact with heat sink?
Improve and eliminate the cause.
Correct connection of connector.
Correct mounting.
Check cabling between IPDU
and CDB and connector.
IPDU P.C. board error
Defect Replace
IPDU P.C. board error
Defect Replace
NO
NO
NO
NO
YES
YES
YES
NO
YES
YES
Are connections of
CDB CN800 and CDB IPDU CN06
connectors normal?
[18 error]
[19 error]
[1C error]* Except RAV-SM560AT-E