7.0 UPS Protection System

7.1

System Protection Features

The preceding one-line schematic illustrates the electrical locations of the protection

devices on all UPS models.

Converter

Inverter

Bypass

Charger/
Chopper

Isolating

XFMR

External

Batteries

Output

Power

MCCB

MBS

Input

Power

Overcurrent

Low Batteryt

Input Abnormal

Overcurrent

Overload

Overvoltage/

Undervoltage

7.2

System Protection Functions

The following chart shows the built-in UPS fault protection functions on all models.

Built-in UPS Fault Protection Functions

Protection Item

Inverter Over-voltage

(IVOV)

Inverter Under-voltage

(IVUV)

UPS Overload

LCD Message

INVERTER

OVERVOLTAGE

INVERTER

UNDERVOLTAGE

OUTPUT OVERLOAD

Cause

Control Malfunction; Feedback Error

Overload or short circuit at the load.

Operation Mode

after Fault

Bypass Operation; Chopper and Inverter Stopped

Inverter Overload: Transfer to bypass; Inverter
stopped.
Bypass Overload: Inverter, Chopper, and Bypass
stopped.

Audible Alarm

Yes: See Audible Alarm Functions

Visible Alarm

Red Fault Lamp “on”

Inverter OL: No Fault Lamp

Bypass OL: Fault Lamp “on”

Relay Contact

Alarm

Fault Relay closed; Bypass Relay closed

Inverter OL: Bypass Relay closed

Bypass OL: Bypass Relay open and Fault relay

closed

Auto-Retransfer

No

Inverter OL: Yes, if bypass ok

Bypass OL: No

Protection Item

Low Battery Voltage

(Level-1)

Low Battery Voltage

(Level-2)

Inverter Output Current Limit

LCD Message

Line-4 will read

“BATTERY LOW”

DC UNDERVOLTAGE

OUTPUT OVERLOAD

Cause

Battery Discharge

Battery Shutdown Level

reached

Load Inrush current

Operation Mode

after Fault

Battery Discharge

Shutdown:

If Bypass ok, transfer to bypass; if not, current-limit
mode

No Output

Audible Alarm

Yes: See Audible Alarm Functions

Visible Alarm

Battery Lamp Flickers

NO

NO

Relay Contact

Alarm

Low Battery Relay

closed

Bypass Relay closed

Auto-Retransfer

No

Yes, if bypass ok

4200FA CT/XT User’s Manual