beautypg.com

8 front panel layout (all units), 9 epo (emergency power off) function, Front panel layout (all units) – Toshiba 4200FA CT/XT User Manual

Page 43: Epo (emergency power off) function, Toshiba

background image

TOSHIBA


6.8

Front Panel Layout (All Units)

Refer to the following illustration for the entire UPS front panel operating procedures.





















line-1
line-2
line-3
line-4

INV

AC IN

BYP

BATT

FAULT

MONI BATT

F1

IN

OUT BATT

TEST

BUZZ
STOP

MENU ENTER

RESET

EPO

STOP

RUN

UPS

4200 Series

ON-LINE

UNINTERRUPTIBLE POWER SYSTEM

4-line liquid
crystal display
screen (see

Section 6.9)

Emergency
power off switch

(see Section 6.6)

STOP/RUN key
switch

Green light emitting
diodes (LED)
(see Section 6.8)

Red light emitting
diode (LED)

(see Section 6.8)

12-key Data entry
keypad (see

Section 6.14)

Green light emitting
diodes (LED)
(see Section 6.11)

12-key Data entry
keypad (see
Section 6.17)

Red light emitting
diode (LED)
(see Section 6.11.1)

STOP/RUN key
switch

Emergency
Power Off switch
(see Section 6.9)

4-line liquid
crystal display
screen (see
Section 6.12)


6.9

EPO (Emergency Power Off) Function

These units are equipped with terminals for receiving an EPO (Emergency Power Off)

"closed contact" switch command from two locations: (1) a remote location and (2) from a

front panel mounted EPO switch. This safety feature enables quick shutdown of the UPS

AC output and battery circuits. Usually the EPO switch is installed in a central location that

is easily accessible to personnel concerned with the operation of the UPS and the

equipment connected to it. The EPO function is initiated by pressing the switch to the

closed "shutdown" position. The effect of using the EPO switch is the same whether the

UPS is in the AC Input Mode, Battery Backup Mode, or the Bypass Mode. See

'EMERGENCY OFF' screen. The following figure shows the UPS condition after

application of the EPO switch. Use the Start-up Procedure for restarting the unit.

Converter

Inverter

Bypass

Charger/
Chopper

Isolating

XFMR

External

Batteries

Output

Power

MCCB

MBS

Input

Power

Power Flow

TRIPPED

OFF

OFF

OFF



4200FA CT/XT User’s Manual

42