beautypg.com

6 4200fa 50kva w/internal transformer, 4200 fa 50kva w/internal transformer, Toshiba – Toshiba 4200FA CT/XT User Manual

Page 37

background image

TOSHIBA

5.6 4200FA 50kVA w/Internal Transformer

Model

Number

T42#3*500#AMXN

Input

# =

(B: 208; H: 220; C: 240; N: 380–415; D: 480; M: 600) VAC

Output

*=

(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye; M:600)

Rated Output Capacity

50 kVA

External Dimensions
W x D x H (cm)

35.5” X 38.3” X 59.3”

(90.1 cm x 97.2 cm x 150.6 cm)

Rated Voltage

208 VAC

Voltage Variation

+10% to -30%; (-15% to -30%) ****

Rated Frequency

50 / 60 Hz

Input Cables Required

3 phase ; 3 Wire + GND

Dual Input Option Cables required

3 phase ; 4 Wire + GND

* Power Factor

Greater than 0.98 when in inverter mode

Required Input kVA

50 kVA

Walk-in Function

From 20% to 100% over 5 seconds

Inrush Current

Less than 8 times the rated current under synchronous operation

Current Limit

115% maximum

Input

* Harmonic Currents

Less than 3% THD

DC Nominal (Voltage Range)

288 VDC (216 to 332 VDC)

Float Charge (Regulation)

324.0 VDC (

± 2%)

Ripple Voltage

0.5 V R.M.S.

**Rated Back-up Time

Refer to Battery System Manual

Battery

Rated Charge Current

11.5 Amps

Rated Voltage

(Determined by Output Transformer internal to the unit)

Rated Current

VA / Nominal Output Voltage / 1.73

Rated Power Factor

0.8 lagging

Output Cables Required

3 phase ; 4 Wire + GND

Voltage Regulation (phase-phase)

± 2% (0–100% balanced load);

± 3% (0–100% unbalanced load)

Voltage Adjustment Range

± 5V Manually from key pad

Phase Displacement

± 2° (0–100% balanced load);

± 4° (unbalanced load)

Rated Frequency

50 / 60 Hz

Frequency Regulation

± 0.1% in free running mode

Frequency Synchronous

± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)

switch selectable by qualified technician

Frequency Slew Rate

1 Hz/s to 3Hz/s(in 0.5 Hz steps)

Voltage Transients
(Recovery time: 50 ms)

± 5% (100% load step change);

± 3% (loss or return of input voltage);

± 8% (transfer of bypass to inverter)

Inverter Overload Capacity

125% 90 sec; 150% 30 sec

Bypass Overload Capacity

1000% 10 ms; 125% 10 min.

Crest Factor

2.5–3.0 within the kW range

Neutral Line Conductor

1.73 (200%) times line rating

Harmonic Voltage Distortion

1.5% max (linear load)

Output

Inrush Current protection

Automatic Transfer to bypass, then retransfer to inverter

Efficiency (Typical)

AC/DC/AC: 81%; DC/AC: 85%

Heat loss to be removed

30,874 BTU/hr (7,778 kcal/hr)

Audible Noise

~65dB @ 1 meter from the front of the unit

Operating Temperature

32 – 104

°F (0 – 40 °C); optimal temperature is 77 °F (25 °C)

Operating Humidity

30–90% RH (non condensing)

Environment

Altitude ***

Less than 2000 meters

Items marked with an (*) are specified at rated conditions under balanced linear loads.

(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.

4200FA CT/XT User’s Manual

36