IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during the installation, maintenance,
and operation of the UPS and its batteries to assure safe and proper operation

1. Turn off, lockout, and tagout all power sources before connecting the power wiring to the

equipment or when performing maintenance.

2. Hardwire type UPS units are not equipped with an over-current protection device, nor do they have

an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be
provided between the UPS output and the load input.

3. Battery servicing should be performed by a qualified TOSHIBA Representative only.

4. Unauthorized personnel should not service batteries.

5. Contact your nearest TOSHIBA authorized service center for battery replacement.

Qualified Personnel ONLY!

Qualified Personnel is one that has the skills and knowledge relating to the construction,
installation, operation, and maintenance of the electrical equipment and has received safety
training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety
requirements).

Qualified Personnel shall

:

1. Have read the entire operation manual.

2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and

equipment, and clear faults in accordance with established safety practices.

3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,

hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.

4. Be trained in rendering first aid.

5. Be knowledgeable of batteries and the required handling and maintenance precautions.

For further information on workplace safety visit www.osha.gov

.


Refer to the Battery System Manual for details on operating and maintaining the battery units for each
system.

UPS System’s output is not equipped with an over-current protection device, or an output disconnect for
the AC output; therefore, a circuit breaker should be provided, by the user, between the UPS output and
the critical load input. This minimum current rating for the device should be rated as follows:

15 kVA

25 kVA

30 kVA

50 kVA

Rated Output

Rating

Rating

Rating

Rating

208/120 VAC

240 V, 60 A

240 V, 90 A

240 V, 110 A

240 V, 175 A

220/127 VAC

240 V, 50 A

240 V, 90 A

240 V, 110 A

240 V, 175 A

240 VAC

240 V, 50 A

240 V, 80 A

240 V, 90 A

240 V, 175 A

380/220 VAC

480 V, 30 A

480 V, 50 A

480 V, 60 A

480 V, 100 A

480/277 VAC

480 V, 25 A

480 V, 40 A

480 V, 50 A

480 V, 80 A

600 VAC

600 V, 20 A

600 V, 35 A

600 V, 40 A

600 V, 70 A

4200FA CT/XT User’s Manual